Technical data

8.1 Basic units RVS...

Rated voltage
Bemessungsfrequenz
Power consumption
External supply line protection
Power supply and outputs
Software class
Mode of operation to EN 60 730
Digital inputs H1 and H2
Analog input H1, H2
Mains voltage S3, 4 and EX2
Sensor input B9
Sensor inputs B1, B3, B12, BX1, BX2
Sensor inputs BX1...BX2
Perm. sensor cables (copper)
with cross-sectional area:
Max. length:
Relay outputs
Rated current range
Max. switch-on current
Max. total current (of all relays)
Rated voltage range
External supply line protection
User Manual
Basic units RVS...
AC 230 V (±10%)
50/60 Hz
RVS46.543: 8 VA
RVS46.530: 8 VA
Fuse slow max. 10 A
...or
Circuit breaker max. 13 A
Characteristic B, C, D according to EN 60898
solid wire or stranded wire (twisted or with
ferrule):
2
1 core: 0.5...2.5 mm
2
2 cores: 0.5. mm
..1.5 mm
3 cores: not permitted
A
1.B (automatic)
safety extra low-voltage for potentialfree low-
voltage contacts:
voltage with contact open:
DC 12 V
current with contact closed:
DC 3 mA
protective extra low-voltage operating range:
DC (0...10) V
internal resistance: > 100 kW
AC 230 V (±10 %)
internal resistance: > 100 kW
NTC1k (QAC34)
NTC10k (QAZ36, QAD36)
PT1000 (optionally for collector and flue gas
sensor)
0.25
0.5
0.75
1.0
20
40
60
80
AC 0.02...2 (2) A
15 A for £1 s
AC 10 A
AC (24...230) V (for potentialfree outputs)
Refer to section "Power supply"
2
2
1.5
mm
120
m
123/138
CE1U2353en
2014-07-30