Programming - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Configuration
Settings
Direct adjustment
Operational lock
Siemens
Building Technologies
5.3.2

Programming

A long press (>3 sec) on the occupancy button enables the service level to be
accessed. The present value blinks when the parameter is selected. Turn the knob to
set the desired value. Select the next setting with a short press of the occupancy
button.
Used as
Display
Function
ru = 1
Room unit addressed as RG1 (default setting)
ru = 2
Room unit addressed as RG2
ru = 3
Room unit addressed as RG3
P1 = 1
Save automatically: (default setting)
A setpoint correction using the know is assumed by either confirming the
operating mode button as without any additional confirmation (timeout)
übernommen.
P1 = 2
Save with confirmation:
A setpoint correction using the knob is assumed only after confirming the
operating mode button.
P2 = 0
OFF: All operating elements released (default setting)
P2 = 1
ON: Following operating elements are locked:
·
Operating mode changeover heating circuit
·
Comfort setpoint adjustment
·
Operating level changeover (occupancy button)
OFF is displayed for 3 seconds when pressing a locked button when operating lock is
active.
The operating lock does not prevent entry to the service level.
User Manual
QAA55..
61/138
CE1U2353en
2014-07-30