Overtemperature protection for the collector

Medium's evaporation temperature

Pump speed
Minimum/maximum

Yield measurement

Antifreeze
Pump capacity
88/138
Siemens
Building Technologies
Line no.
Operating line
3850
Collector overtemp prot
If there is a risk of overtemperature at the collector, storage tank charging is continued
to reduce the amount of surplus heat. When the storage tank safety temperature is
reached, charging will be stopped.
T
Tkol
TSpSi
TSp
On
Off
TSpSi
Storage tank safety temperature
TSp
Storage tank temperature
TKolUe
Collector temperature for overtemperature protection
TSpmax
Maximum charging temperature
Tkol
Collector temperature
On / Off
Collector pump
T
Temperature
t
Time
Line no.
Operating line
3860
Evaporation heat carrier
If there is a risk of the heat carrying medium evaporating due to high collector
temperatures, the collector pump will be deactivated to prevent it from reaching
excessive temperatures. This is a protective pump function.
The solar pump motor speed is limited by a minimum and maximum permitted speed.
Line no.
Operating line
3880
Antifreeze
3881
Antifreeze concentration
3884
Pump capacity
The 24-hour and total solar energy yield (operating lines 8526 and 8527) is calculated,
based on these data.
Since the mixing ratio of the collector medium has an impact on heat transmission, the
type of antifreeze used and its concentration must be entered in order to be able to
determine the energy yield.
The flow rate in l/h of the pump used must be determined and serves for calculating the
volume delivered.