Electric immersion heater

electric immersion
heater:operating mode
Electric immersion heater
release
90/138
Siemens
Building Technologies
Line no.
Operating line
5060
El imm heater optg mode
Substitute
Summer
Always
5061
El immersion heater release
24 h/day
DHW release
Time program 4/DHW
5062
El immersion heater control
External thermostat
DHW sensor
Substitute
The electric immersion heater is only used if the heat generation delivers a fault status
message or if it has been shut down via heat generation lock. This means that in
normal situations the DHW is always heated by the heat generation.
Summer
The electric immersion heater is used as soon as all connected heating circuits have
switched to summer operation. The DHW is again heated by heat generation as soon
as at least one of the heating circuits has switched back to heating operation. The
electric immersion heater is also used if the heat generation delivers a fault status
message or if it has been shut down via heat generation lock.
Always
DHW is heated with the electric immersion heater throughout the year. This means that
with this application, heat generation never required for DHW heating.
24 h/day
The electric immersion heater is always released, independent of time programs.
Example:
DHW release
The electric immersion heater is switched on and off according to DHW release.
Example:
Time program 4/DHW
For the electric immersion heater, time program 4 / DHW of the local controller is taken
into account.