End of summer
compensation at OT
Summer compensation
setpoint increase

Flow temperature setpoint limits

Min. flow setpoint

Room influence

Compensation variants
Siemens
Building Technologies
Summer compensation takes full effect at this outside temperature (920). The comfort
setpoint is not affected by any further increase in the outdoor temperature.
This setting determines the maximum permissible increase in the comfort setpoint.
TRKw
902
918
TRKw
Cooling setpoint
TA
Outside temperature (OT)
Line no.
Operating line
923
Min. flow setpoint at OT 25°C
924
Min. flow setpoint at OT 35°C
A low limit can be defined for the cooling flow temperature.
The limit curve is determined by defining two fixed points.
There is also a low limit for the resulting flow setpoint, which must not fall below 5 °C.
This defines the lowest permissible flow temperature at a composite outside
temperature of 25°C/25°C.
If there is no valid outside air temperature available, the controller uses the value
"Flow setpoint min TA = 35°C"
TVKw
923
924
25°C
TVKw
Flow temperature setpoint for cooling (with low limit control)
TVKw_unb Flow temperature setpoint for cooling (without low limit control)
TAgem
Composite outside temperature
Line no.
Operating line
928
Room influence
User Manual
Cooling circuit
920
919
TA
TVKw
TVKw_unb
35°C
TAgem
79/138
CE1U2353en
2014-07-30