Optimum start / stop control

Optimum start control max
Optimum top control max

Raising the reduced setpoint

Siemens
Building Technologies
Line no.
HC1
HC2
HCP
790
1090
1390
791
1091
1391
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint is reached at the relevant switching time.
The change from one temperature level to the other is optimized in a way that the
Comfort setpoint minus 1/4 °C is reached at the relevant switching time
· Optimum start / stop control is possible with or without room sensor.
0
Xein
TRx
TRw
Xein
Switch-on time shifted forward in time
Xaus
Switch-off time shifted forward in time
ZSP
Time program
TRx
Actual value of room temperature
TRw
Room temperature setpoint
Line no.
HC1
HC2
HCP
800
1100
1400
801
1101
1401
The function is used primarily in connection with heating systems with only little spare
capacity (e.g. low-energy houses). In such cases, the heating up time would be too
long at low outside temperatures. When the Reduced setpoint is raised, the rooms are
prevented from cooling down to too low levels, thus shortening the heating up time
when changing to the Comfort setpoint.
User Manual
Heating circuits
Operating line
Optimum start control max
Optimum stop control max
ZSP
Operating line
Red setpoint increase start
Red setpoint increase end
Xaus
1/4 °C
CE1U2353en
24
73/138
2014-07-30