Manual operation

Setpoint adjustment in
manual control

Simulations

110/138
Siemens
Building Technologies
Line no.
Operating line
7140
Manual control
When manual control is activated, the relay outputs are no longer energized and
deenergized according to the control state but are set to a predefined manual control
state in accordance with their functions (see table below).
The burner relay energized in manual control can be deenergized by the electronic
temperature controller (TR).
Designation
Solar
Collector pump
DHW
Charging pump
Diverting valve
Mixing pump
Intermediate circuit pump
Mixing valve opening /
closing
Instantaneous DHW heater
pump
Instantaneous DHW heater
on / off
Circulating pump
electric immersion heater
Heating circuit 1...3
heating circuit pump
Heating circuit mixing valve
opening / closing
Heating circuit pump 2nd
speed
Cooling circuit 1
Cooling circuit pump
Cooling circuit mixing valve
opening / closing
Diverting valve for cooling
Primary controller
System pump
Mixing valve opening /
closing
Hx group
Pump H1
Pump H2
Pump H3
Auxiliary functions
Alarm output
Time program 5
Heat demand
Refrigeration demand
Storage tank transfer pump
After manual control has been activated, a change to the basic display must be made.
There, the maintenance / special mode symbol
Press the info button to switch to info display "Manual mode", where the setpoint can be
adjusted.
Line no.
Operating line
7150
Simulation outside temp
To facilitate commissioning and fault tracing, outside temperatures in the range from –
50 to +50°C can be simulated. During simulation, the actual, the composite and the
attenuated outside temperature will be overridden by the set simulated temperature.
During simulation, calculation of the 3 mentioned outside temperatures continues and
the temperatures are available again when simulation is completed.
The function is deactivated by setting -.- on this operating line, or automatically after a
timeout of 1 hour.
User Manual
Maintenance / special mode
Relay
State
Q5
Off
Q3
On
Q3
Off
Q32
Off
Q33
On
Y31/Y32
Off
Q34
On
Y33/Y34
Off
Q4
On
K6
On
Q2
On
Q6
Q20
Y1 / Y2
Off
Y5 / Y6
Q21
On
Q22
Q23
Q24
On
Y23/Y24
Off
Y21
Off
Q14
On
Y19/Y20
Off
Q15
On
Q18
On
Q19
On
K10
Off
K13
Off
K27
On
K28
Off
Q11
Off
appears.
CE1U2353en
2014-07-30