Charging controller (dT)

Start function

Min run time collector
pump
Collector start funct
gradient

Frost protection for the collector

Siemens
Building Technologies

6.11 Solar

Line no.
Operating line
3810
Temp diff on
3811
Temp diff off
3812
Charg temp min DHW st tank
For charging the storage tank via the heat exchanger, the temperature differential
between collector and storage tank / swimming pool must be sufficient , and the
collector must have reached the minimum charging temperature for the storage tank /
swimming pool .
T
On
OFF
Tkol
Collector temperature
On / Off
Collector pump
SdOn
Temperature differential ON
SdOff
Temperature differential OFF
TSp
Storage tank temperature
TLmin
Charging temp min DHW storage tank / buffer / swimming pool
Line no.
Operating line
3831
Min run time collector pump
3834
Collector start funct gradient
The function periodically activates the collector pump for at least the selected minimum
running time.
When the temperature at the collector sensor rises, the collector pump is activated.
Line no.
Operating line
3840
Collector frost protection
When there is risk of frost at the collector, the collector pump will be activated to
prevent the heat-carrying medium from freezing.
·
If the collector temperature falls below the frost protection temperature, the
collector pump will be activated: TKol < TKolFrost.
·
When the collector temperature returns to a level of 1°K above the frost protection
temperature, the collector pump will be deactivated again: TKol > TKolFrost + 1.
User Manual
Solar
Tkol
SdEin
SdAus
TSp
TLmin
t
CE1U2353en
2014-07-30
87/138