Radio Repeater Avs14.390; Mounting Method; Connections; Radio Connection - Siemens Albatros RVS46 Series User Manual

Zone controller
Table of Contents

Advertisement

Mounting method

Connections

Radio connection

Establishing the link
Testing

Dimensions and drilling plan

30/138
Siemens
Building Technologies
3.8.4

Radio repeater AVS14.390

· To establish the radio connection, the device must be provisionally connected to
power prior to mounting, enabling the radio connection to be opened and tested.
· The radio repeater must be fitted inside the building.
1
2
Power is supplied via the enclosed power pack. The wires are interchangeable.
Make the radio connection in the vicinity of the radio module prior to mounting so that
all systems are within easy reach.
Prerequisite for the radio connection is that all components receive power, which
means that the radio module must be correctly connected to the basic unit and power
must be correctly supplied to the radio repeater.
8. Press the button on the radio module for at least 8
seconds until the LED on the radio module starts
flashing at high frequency.
9. Press the button on the installed radio repeater until
the LED start flashing at high frequency.
10. The connection is established when the LED on the
radio module extinguishes.
The test is made to check the quality of the radio link.
· The test can be aborted by pressing the ESC button.
· While the radio link can be opened on the controller, the test should be made at the
location where the room unit will be installed
11. Press button 3 on the radio repeater for a maximum of 8 seconds until the LED
starts flashing at low frequency.
12. When radio communication works, the LED on the radio module flashes briefly at
10-second intervals.
13. After the test, press the button on the radio repeater again briefly until the LED
extinguishes.
90
User Manual
Wireless components
32
4
Button
4,2
2
1
56
60
CE1U2353en
LED
2014-07-30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents