System Timings - Honeywell ESSER Fire Alarm Control Panel Compact Commissioning Instruction

Table of Contents

Advertisement

Fire Alarm Control Panel Compact
6.2

System timings

System-dependant switching times can be configured in this menu.
2
System timings
1 daylight saving time
2 daylight saving start: 30.03.15 02:00
3 daylight saving end
- delay common fault (min) : 00
5 delay mains fault (min)
- sync. Bus alarm (s)
7 alarm suppression (s)
system timings
1 delay time (s)
2 verification time (s) : 0040
Fig. 48: >System timings< menu screens
Summer time (1,2,3)
The summer time ON/OFF setting determines whether or not the fire alarm control panel should automatically
switch between summer time and winter time at the programmed time. The switching points for the ON/OFF
switching must be entered.
daylight time start
1 date
:
25.03.12
2 time
:
02:00
3
daylight time start
1 date
:
25.03.12
2 time
:
02:00
3
Fig. 49: >Daylight time start< menu screen
34
ABC
1/2
: on
Menu page 1 of 2
: 26.10.15 02:00
: 030
: 020
: 010
3
2/2
Menu page 2 of 2
: 0010
3
1
Summer time start/end
Enter the date (1) on which the switching to summer time
(+1 hour) should occur. The date is entered with the numeric
keys.
3
Example: 250312  25 March 2012
1
Enter the time (2) at which the switching to summer time
(+ 1 hour) should occur.
3
Example: 0200  02:00 am
ESC 
The next step is to enter the desired switching time
for >summer time end< for the automatic switching (-1 hour).
save entry (continue with ESC)
cancel entry and exit sub-menu
FB 798238.GB0 / 10.14