Revision Menu - Honeywell ESSER Fire Alarm Control Panel Compact Commissioning Instruction

Table of Contents

Advertisement

Fire Alarm Control Panel Compact
8

Revision menu

This function allows service work on the fire alarm control panel without triggering an external alerting.
main menu
1 information
2 overview
3 operate
4 service
5 revision
3
revision
1 on
2 off
3
Fig. 61: >Revision< menu screens
Press key  Revision ON
1
The 'DISABLEMENT' LED and the (yellow) LED for Fire Department alarm, Sounder and Fire
Protection Equipment (if a trigger prevention is programmed) blink on the control panel.
Press key  Revision off
2
The FACP is in normal mode again.
Only authorised and instructed persons may operate an installed and ready-for-alerting fire alarm
control panel and such persons must then operate the FACP in accordance with safety
precautions and, if applicable, the instruction of the emergency service (i.e. local fire brigade).
In the Revision mode, the Alarm Transmission Unit (ATU) and all other external alerting and fire
protection equipment may not be activated, depending on the configuration.
40
Select the >Revision< function with the
3
3
5
key.
JKL
FB 798238.GB0 / 10.14