Honeywell ESSER Fire Alarm Control Panel Compact Commissioning Instruction page 36

Table of Contents

Advertisement

Fire Alarm Control Panel Compact
6.2.1 Delay time / verification time
This function allows a delayed activation of the transmission unit (ATU) and the alarm signalling devices and fire
protection equipment in the day mode of the FACP.
This function can be used, for example, for areas and buildings in which persons are present and who can, in
the event of a fire alarm, prevent a direct alerting by pressing the >verification< key and use the remaining
(programmable) verification time until the automatic alerting, to ascertain why the alarm was triggered (see also
the Operating Instruction, Part No. 798236.GB0).
Switch ON/OFF day/night mode (if programmed).
Start verification time.
system settings
1 delay time (s)
2 verification time (s)
system settings
1 delay time (s)
2 verification time (s)
Fig. 53: >Delay time< menu screen
Reset the FACP
The transmission unit (ATU) of the alarm signalling devices and fire protection devices will be automatically
activated after the elapse of the delay and verification time if the alarm signal was not reset by pressing the
'panel reset button' in order to cancel the alarm signal and thus prevent the activation.
A manual alerting via the hand-operated fire alarm buttons is possible at any time and results in a direct
activation depending on the programming.
In the case of further (two or more) fire alarms, the delay time is ignored and the alerting is activated
immediately.
The delay and verification time must be programmed building-specifically and in accordance with the current
German VdS directives and local requirements. The German VdS directives permit a maximum total delay
(verification time + delay time) of 10 minutes (
Observe standards and requirements!
Observe the information on the configuration and commissioning of the fire alarm control panel in
accordance with national standards/directives and local requirements.
This function may not be permissible or the programmable time may have to be set in accordance
with local requirements, depending on the specific use of the system or the country in which the
system is used.
36
Example: delay time
2/2
: 0010
: 0040
Enter desired delay time in the range 0000-9999 seconds for
the external alerting.
3
"0000' entry"  no delay
1
Example: verification time
2/2
:
0600
: 1200
Enter the desired verification time in the range 0000-9999
seconds for the verification of the alarm cause.
3
"0000" entry  no delay
ESC
1
 save entry (continue with ESC)
 cancel entry or exit sub-menu
600 seconds permissible).
2
ABC
FB 798238.GB0 / 10.14