Honeywell ESSER Fire Alarm Control Panel Compact Commissioning Instruction page 18

Table of Contents

Advertisement

Fire Alarm Control Panel Compact
5.4.1
one-type control input
Z
If control input was selected as type, two functions can be defined for both the coming and going event.
type
1 fire
2 techn. alarm
3 pre-alarm
4 fault
5 control input
6 system input
7 unused
zone <-0021->
1 type
:
control input
2 hardware
:
IN_1
3 latched
:
off
4 crtl. funct.
:
0 coming / 0 going
5 label 1 : [ATU activated
6 label 2 : [IN_1 Mainboard
3
1 coming 1
: panel reset
2 going
1
: none
3 coming 2
: none
4 going
2
: none
5 coming 3
: none
6 going
3
: none
7 coming 4
: none
8 going
4
: none
Fig. 28 : >Control input< menu screens
18
3
5
JKL
]
]
3
4
GHI
3
to
1
8
TUV
function
1 delay on
2 delay off
3 sound on
4 sound off
5 start evacuation
6 stop evacuation
7 signal 1 on (IQ8)
function
1 signal 2 on (IQ8)
2 signal 3 on (IQ8)
3 signal 3 on (IQ8)
4 signal off (IQ8)
5 disable control
6 enable control
7 line on
function
1 start OTG testmode
- start verification mode
3 start testmode zone
4 O-sensor line off
5 G-sensor line off
6 sensors line on
7 O-sensor zone off
function
1 G-sensor zone off
2 sensors zone off
3 zone/detector on
4 sensor detector off
5 zone/detector off
6 zone/detector on
- start verification mode line
function
1 none
3
3
3
3
3
FB 798238.GB0 / 10.14