Delay on common fault in minutes
system timings
1 daylight saving time
2 daylight saving start: 25.03.12 02:00
3 daylight saving end
4 delay common fault (min) : 15
5 delay mains fault (min)
- sync. Bus alarm (s)
- alarm suppression (s)
Fig. 50: >Delay common fault< menu screen
Delay on mains failure in minutes
system timings
1 daylight saving time
2 daylight saving start: 25.03.12 02:00
3 daylight saving end
4 delay common fault (min) : 15
5 delay mains fault (min)
- sync. Bus alarm (s)
- alarm suppression (s)
Fig. 51: >Delay mains fault< menu screen
Observe standards and requirements!
Observe the information on the configuration and commissioning of the fire alarm control panel in
accordance with national standards/directives and local requirements.
This function may not be permissible or the programmable time may have to be set in accordance
with local requirements, depending on the specific use of the system or the country in which the
system is used.
Alarm suppression in seconds
system timings
1 daylight saving time
2 daylight saving start: 25.03.12 02:00
3 daylight saving end
4 delay common fault (min) : 15
5 delay mains fault (min)
- sync. Bus alarm (s)
- alarm suppression (s)
Fig. 52: >Alarm suppression< menu screen
save entry
ESC 
cancel entry or exit sub-menu
FB 798238.GB0 / 10.14
4
GHI
A system common fault message will be suppressed for the set
1/2
time (00-99 minutes). No message display or activation will
: on
occur during this time. The message will be displayed and the
: 28.10.12 02:00
assigned outputs activated if the fault cause still exists after the
: 30
: 0
set suppression time has elapsed.
: 000
3
"00" entry  no delay
5
JKL
A mains supply fault will be suppressed for the set time
1/2
(00-99 minutes). This option is suitable for not displaying short-
: on
term mains failures as a fault.
: 28.10.12 02:00
: 30
: 0
"00" entry  no delay
: 000
3
If an alarm is detected during the 3 seconds shown here, after
1/2
a reset of the FACP, no alarm from the detector will be shown
: on
on the control panel or analysed but instead only a pre-alarm.
: 28.10.12 02:00
: 30
: 0
: 000
3
Fire Alarm Control Panel Compact
35