Battery Information; Earth Fault Information - Honeywell ESSER Fire Alarm Control Panel Compact Commissioning Instruction

Table of Contents

Advertisement

4.2

Battery information

Information on the batteries of the emergency power supply is shown in the display. The permissible limit values
are shown in the brackets.
battery information
1 refresh
main board
voltage in V
int. resistance mOhm [< 600] : 290
temp. (degree C)
[-5...+45] : 24.0
charging current
3
Fig. 16: >Battery information< menu screen
4.3

Earth fault information

The current measurement value for the earth fault monitoring is shown in the display. A fault alarm occurs if an
earth fault measurement is outside of the tolerance range. The earth fault measurement can be switched off
(ON) permanently or temporarily for commissioning or service work in order to suppress fault alarms. All other
fault alarms can be diverted via the fault output. The earth fault monitoring can also be switched off.
earth fault information
1 suppress earth fault information
lower threshold : 10539
upper threshold : 18539
nominal value
: 13539
actual value
: 13500
3
Fig. 17: >Earth fault information< menu screen
suppress earth fault information
1 status
: off
2 duration (days) : 99
3
Fig. 18: >Suppress earth fault information< menu screen
A time period (in days) can be selected if the suppression of the earth fault information is switched on. The earth
fault measurement is switched off and the display of the fault is suppressed during this period. The remaining
days of the period are shown in the "Duration in days" line.
suppress earth fault information
1 status
: off
2 duration (days) : 99
3
Fig. 19: >Duration in days< menu screen
Observe standards and local requirements!
Observe the information on the configuration and commissioning of the FACP in accordance
with national standards/directives and local requirements.
The set earth fault information suppression is automatically deleted if a different configuration
template is selected.
FB 798238.GB0 / 10.14
1
1/2
[>21.2] : 26.9
[<1.4] : 0.0
3
Select >Suppress earth fault information< menu item.
3
Suppression of the earth fault information:
Status OFF:
Status ON:
3
2
3
Fire Alarm Control Panel Compact
Select the >Refresh< function.
In this example, the current battery voltage is 26.9 V
and in the permissible range of > 21.2 V.
A battery fault alarm occurs if the battery voltage is less
than < 21.2 V.
 Display of the earth fault measurement
(factory default)
 Earth fault information suppressed
Switch on earth fault information suppression (ON)
A number between 0 and 99 can be entered directly
after the "Duration in days" menu item has been
selected.
The remaining time will be automatically displayed if
a suppression has already been set. This value can
be increased or reduced.
13