Fire Alarm Control Panel Compact
6
Settings
5
settings
1 display functions
2 system timings
3 control timings
4 language
3
Fig. 44: >Settings< menu screen
6.1
Display functions
display functions
1 descript. : [panel 1
2 code installer
3 code operation
code cust. data
- country spec. : germany
- fault evaluation MZD/MDD : on
- disable MZD/MDD
3
display functions
- reset fauls if panel reset
- indicate pre-alarm detector
- disable HMI monitoring
- diagnostic notice detector
- buzzer technical alarm
- buzzer cover contact
- buzzer pre-alarm
display functions
1 buzzer verification time : off
2 acoustic mute
Fig. 45: >Settings< menu screens
Observe standards and requirements!
Observe the information on the configuration and commissioning of the FACP in accordance with
national standards/directives and local requirements.
32
JKL
3
1
1/3
]
: 123
: 0123
: 0815
3
2/3
: off
: on
: off
: on
: off
: off
: off
Acoustic mute available
3/3
: on
Switching this function On or Off programs the "acoustic
alarm device" (buzzer) key to have either a mute or alarm
device switch-off effect.
3
The buzzer switch-off or muting is shown in each case with
the yellow LED on the control panel.
Switch-off
Mute:
2
ABC
Switch-off /mute acoustic alarm devices
acoustic alarm devices are switched off
and will not be activated by an alarm
event.
The triggered acoustic alarm devices
were reset and muted. They will be
triggered with each new alarm signal.
FB 798238.GB0 / 10.14