Omron SYSMAC CPM2B Operation Manual page 80

Hide thumbs Also See for SYSMAC CPM2B:
Table of Contents

Advertisement

Wiring and Connections
High-speed Counter Input Connection Examples
Differential Phase Mode
(Count frequency: 5 kHz)
E6B2-CWZ6C
Encoder
Black
(NPN open-col-
lector output)
White
Orange
Brown
Blue
Leakage Current
62
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Special functions for input bits IR 00003 through IR 00006 are set in
DM 6628:
Bit
Bits in
address
DM 6628
IR 00003
00 to 03
IR 00004
04 to 07
IR 00005
08 to 11
IR 00006
12 to 15
CPM2B
00000 A-phase input
00001 B-phase input
00002 Z-phase input
COM
24 V DC
A leakage current can cause false inputs when using 2-wire sensors (proxim-
ity switches or photoelectric switches) or limit switches with LEDs. False
inputs won't occur if the leakage current is less than 1.0 mA (2.5 mA for
IN00000 to IN00002). If the leakage current exceeds these values, insert a
bleeder resistor in the circuit to reduce the input impedance, as shown in the
following diagram.
2-wire sensor, etc.
I: Device's leakage current (mA)
R: Bleeder resistance (kΩ)
W: Bleeder resistor's power rating (W)
The equations above were derived from the following equations:
R ×
I ×
R +
Input voltage (24)
W ≥
Refer to2-1-3 I/O Specifications for details on the values L
The input impedance, input current, and OFF voltage may vary depending on the
input being used. (IN00000 through IN00002 have different values.)
PLC Setup setting (in DM 6628)
0
Used as normal
Used as interrupt
inputs.
inputs (including
counter mode).
Pulse Plus Direction Input mode
(Count frequency: 20 kHz)
E6A2-CS5C
Encoder
Sensor or
switch
Sensor or
switch
Input power
supply
R
Bleeder
resistor
L
I
C
E
× 5.0
L
C
kΩ max.
R =
I × L
− 5.0
C
Input voltage (24)
Input Current (I
)
C
≤ OFF voltasge ( E
Input voltage (24)
Input Current (I
)
C
× Input voltage (24) × tolerance (4)
R
Section 3-5
1
Used as quick-
response inputs.
CPM2B
00000 Pulse input
00001 Direction input
00002 Reset input
Sensor
power
COM
24 V DC
CPM2B
: CPM2B's input impedance (kΩ)
C
: CPM2B's input current (mA)
: CPM2B's OFF voltage (V) = 5.0 V
C
2.3 W min.
W =
R
: 5.0)
C
, I
, and E
.
C
C
C
2