Wiring and Connections
Compatible Wires and Terminals
Note
3-5-2

I/O Wiring Procedures

Removing and Wiring I/O Terminal Blocks
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Wire/terminal
Solid wire
Stranded wire
Two-conductor
Solid
wires
Stranded
Stranded with
pin terminal
Pin terminals
The following diagram shows how to wire the power supply.
24 V DC
(12 V DC)
1. Do not perform a voltage withstand test on the DC power supply terminals.
The test might damage the PLC's internal components.
2. When equipment must conform to the EC Directives (Low-voltage Direc-
tives), use a power supply with double insulation or reinforced insulation.
The following tables provide output terminal block specifications.
CPU Boards and Expansion I/O Boards
with relay outputs
Specification
2
0.2 to 2.5 mm
(AWG 24 to AWG 12)
Strip 7 mm (1/4 inch) of insulation.
2
0.2 to 2.5 mm
(AWG 24 to AWG 12)
Strip 7 mm (1/4 inch) of insulation.
2 × (0.2 to 1.0 mm
2
) (AWG 24 to AWG 20)
2 × (0.2 to 1.5 mm
2
) (AWG 24 to AWG 16)
2 × (0.25 to 1.0 mm
2
) (AWG 24 to AWG 20)
without an insulating sleeve
2
0.2 to 2.5 mm
diameter, 7-mm long pin terminal
The power supply terminal
block is removable.
0 V
Output terminal blocks
Section 3-5
53