Rinnai RS100 Training Program page 40

Condensing boiler controller
Table of Contents

Advertisement

Troubleshooting
• When troubleshooting with an RS100, consider the following:
• Jumping the thermostat terminals (22 and 23) to force the boiler to fire will do nothing unless the RS100
is disconnected from 20 and 21
• If the RS100 is not set for RC, the room conditions will not influence the boiler
• If the RS100 is set for RC, outside temperature will not influence the boiler except for freezing or summer
setback conditions
• If max temp at the boiler is lower than the max temp at the RS100, the boiler's value will have
precedence
• If there is a complaint of lack of heating or too much heat (heating or DHW mode)
• First, ensure the boiler functions correctly without an RS100 and there are no system issues
• If there is a diverter valve on the boiler, ensure it is in the right position and functioning correctly
• Ensure clock settings are correct (including the temp) and heating when needed
• Ensure the RS100 is not physically located in an environment that could cause it to report invalidly (if
in RC mode only)
• Ensure vacation, absent, setback, or standby modes aren't selected (lack of heating)
• Ensure boiler max and min temps are correct
• Ensure DHW settings are correct
• Ensure UC Para 1 is set to RED (lack of heating)
• Ensure party mode isn't engaged (too much heat)
• If needed, validate all parameters-reset to factory defaults if needed (make sure system unique
parameters are then reset)
www.rinnai.us • © 2009 Rinnai America Corporation
40

Advertisement

Table of Contents
loading

Table of Contents