Rinnai RS100 Training Program page 32

Condensing boiler controller
Table of Contents

Advertisement

Unmixed (HC) Circuit Parameters
(continued)
PARA
Description
Min. temp
12
limit
Max. temp
13
limit
NOTE: If parameter 1 in the boiler is lower, it will override this setting; NOTE: This value will go to 203°F but the
boiler will never eclipse 176°F; NOTE: 176°F=Default at shipment, 158°F=Default at System Reset
14
NA
23
NA
24
NA
Daytime
25
room temp
base value
Nighttime
26
room temp
base value
K-Factor
27
(curve slope)
Range / Explanation
50°F to max
Minimum boiler temperature limit in heating
temp
mode NOTE: This overrides Boiler Para 27
Min. temp
Maximum boiler temperature limit in
to 176°F
heating mode.
-9 to 36°F
Not for use with the RS100. Do not adjust
1 to 100
Do not adjust (temp)
5–240
Do not adjust (minutes)
Daytime base value for room temp (Note:
41 to 86°F
This setting is not needed as there is a
button on the front for it)
Nighttime base value for room temp (Note:
41 to 86°F
This setting is not needed as there is a
button on the front for it)
Higher number=steeper the curve.
NOTE: this can be adjusted from
0.2 to 3.5
the front panel button. It is not
needed if Para 3=1 and Para 4=RC.
www.rinnai.us • © 2009 Rinnai America Corporation
Factory
User
Setting
Access
68°F
No
176°F
No
0°F
No
8
No
15
No
70°F
Yes
61°F
Yes
1.50
Yes
32