Rinnai RS100 Training Program page 26

Condensing boiler controller
Table of Contents

Advertisement

System Parameters (continued)
PARA
Description
Summer
4
setback
temperature
System frost
5
protect
Climate
9
Zone
Building
10
construction
NOTE: Light Construction = default at shipment, medium = default at system reset; This parameter does not
Range / Explanation
OFF
No summer setback
System frost
When the outdoor sensor detects the
setting (Para
selected temperature, the heating side of
5) to 86°F
the boiler will not operate
OFF
No function
-4°F to
When the outdoor sensor detects the
Summer
selected temperature, pump circulation
setback
will begin. This overrides parameter 23 in
(Para 4)
the boiler.
Outdoor design temperature-this is
determined by the geography of the
-4°F to 68°F
installation. This overrides parameter 7
inside the boiler. It is not needed when the
RS100 is in RC mode.
1
Light Construction
2
Medium Construction
3
Heavy (Tight) Construction
have an effect if in RC mode
www.rinnai.us • © 2009 Rinnai America Corporation
Factory
User
Setting
Access
68°F
Yes
37°F
No
10°F
No
1
No
26