Rinnai RS100 Training Program page 30

Condensing boiler controller
Table of Contents

Advertisement

Unmixed (HC) Circuit Parameters
PARA
Description
Controller
application
type
3
(Outdoor
reset or RC
mode)
If OFF or 3 is selected the boiler's pump continuously operates. The boiler will fire based on the outside sensor.
NOTE: 1=Default at shipment, 3=Default at System Reset
Controller
effect type
4
(Parameter 3
must be set
to 1)
5
N/A
Range / Explanation
Outdoor reset mode: The RS100 doesn't use the
OFF
room temp for operation. Boiler supply temp is
displayed (pressing the dial displays room temp).
Room Control/RC Mode: Controller fully enabled
1
(recommended)
Outdoor reset mode: The RS100 doesn't use the
3
room temp for operation but it will be displayed
The boiler's pump continuously operates. The
OFF
boiler will fire based on the outside sensor. Boiler
supply temp is displayed.
10-
Do not use these settings
500%
The boiler will operate based only on the
RC
RS100's area temperature sensor
NOTE: RC=Default at shipment, OFF=Default at System Reset
OFF
This should not be altered
/ON
www.rinnai.us • © 2009 Rinnai America Corporation
(continued)
Factory
User
Setting
Access
1
Yes
RC
Yes
OFF
Yes
30