Rinnai RS100 Training Program

Rinnai RS100 Training Program

Condensing boiler controller

Advertisement

Quick Links

Condensing Boiler
RS100 Controller Training Program
Training Program #501102A –
062311
www.rinnai.us • © 2009 Rinnai America Corporation

Advertisement

Table of Contents
loading

Summary of Contents for Rinnai RS100

  • Page 1 Condensing Boiler RS100 Controller Training Program Training Program #501102A – 062311 www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 2: Features And Benefits

    RS100 –Programmable Wall Thermostat with room setback • The RS100 connects directly to the boiler and acts as a central thermostat for the entire structure • Direct communication with the boiler allows it to fire based on the area’s immediate needs •...
  • Page 3: Scope Of Use

    Applications for the RS100 Room controller The RS100 is a room controller and not an on/off room thermostat. It is intended to work only with Rinnai boilers. When used in conjunction with a Rinnai boiler it will sense the room temperature and use it to influence the supply water temperature.
  • Page 4 Scope of Use- Single Zone System (RC mode) The RS100 can be used to control a single heating zone system. A single heating zone system has only one loop of heating. The placement of the RS100 is very important; it must be placed in the coldest room within the single zone system.
  • Page 5 Controller theoretical temperature for comfort. In this application, the RS100 will allow the boiler to switch between day and night outdoor reset curves. The boiler is then operating with constant circulation and no input from room thermostats (on/off) or third party controls.
  • Page 6 (on/off) or third party controls. The third party control panel cannot be connected to the boiler with an RS100 also connected. Boiler thermostat terminals 22 and 23 are inactive when the RS100 is connected. www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 7: Installation

    BASICS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 8: Electrical Connections

    Electrical Connections Below is the connection for the RS100. Please refer to the installation manual and Rinnai’s recommended application guide for more details or contact Rinnai’s Engineering Department as needed Outdoor reset sensor (included with boiler) On/Off room Release the tab at connects here.
  • Page 9 OPERATION THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 10 ―GB‖ 10/09) the controller will not Pressing the dial will exit the exit this page language display quicker www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 11 Turning the dial will move to other settings that can be altered on that page Pressing the Information button will move to the previous page Continually pressing the information button will ultimately move back to the operation page www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 12 (P1-P3), this clock with I, II, or III will indicate Time Status bar indicating current operating mode (currently which program is (24 hour clock) indicating boiler is operating in timer mode) currently selected www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 13 (100°F default). NOTE: While in these modes, a brief press of the dial will allow immediate temperature adjustment. NOTE: During normal operation in RC mode, the area/room temperature is displayed—not the set point. www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 14 In this mode, heating will not operate—frost protection is enabled. NOTE: During normal operation in RC mode, the area/room temperature is displayed—not the set point. www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 15 If the user wants to adjust this (because the area does not seem to heat well) it should be done in increments of 0.10 every 2 days to allow the boiler time to adjust to the changes. Outside Temperature (F) www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 16 NOTE: Holding the Info button for 3 seconds will allow adjustment of the time these values will display (0.5-10 minutes). OFF will allow the display to follow the System setting (default 2 minutes). www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 17 Briefly pressing this button displays current DHW set point. Turning the dial will adjust this value. The dial must then be pressed to enter the new value www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 18 Operational mode is changed to a one-time hot water boost while in setback. This value can be adjusted from 0.5 to 240 minutes. When the boost time or day time DHW temperature is reached, DHW is maintained again at the setback temperature. www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 19: Installer Settings

    INSTALLER SETTINGS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 20: Parameter Access

    DHW buttons accessible simultaneously for 3 seconds for • After 2 Minutes of inactivity, these menus will be installer level exited automatically (this value can be changed) access www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 21 • ALARM—Allows display of last five errors • This chapter is not available at the consumer level • SENSOR ADJUSTMENT—Allows calibration of the RS100 temperature sensor • This chapter is not available at the consumer level • TIME / DATE—Allows changes to current time and date...
  • Page 22: Time Programs

    • If a second or third event is added, the day and ―2‖ or ―3‖ will display • ―3‖ will not display until a second event is entered • ―2‖ or ―3‖ will not display if the previous event ends at 24:00 (midnight) www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 23 • Dial the rotary button backwards (CCW) one click • The copy feature will be visible • From one day to Saturday and Sunday (6-7) • From one day to the entire week (1-7) www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 24: Hydraulic Parameters

    Unmixed (heating) Constant control-this forces the boiler to circuit assignment operate at the max temperature—set at Para 12 in the Unmixed Circuit Chapter. This could reduce efficiency and comfort. (This is not recommended) www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 25: System Parameters

    CH of CH/DHW or DHW before entering a specific operational mode. Under normal operation the status bar for operational mode will not be visible www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 26 Light Construction Building Medium Construction construction Heavy (Tight) Construction NOTE: Light Construction = default at shipment, medium = default at system reset; This parameter does not have an effect if in RC mode www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 27 Example: At the User Level, only parameters accessible by the user are reset Reset to Reset factory values • Time and date will not be reset • Language will default to German, GB must be set at initialization for English www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 28: Dhw Parameters

    NOTE: This value will go to 203°F but the boiler will never eclipse 176°F; NOTE: During a split load between heat and DHW, the supply temp is based on DHW needs—do not use on direct-coupled in-floor radiant systems This should not be altered 131°F www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 29 (night time operate unless this freezing threshold setback) temperature is detected operation Reduced-HC will operate on the night time heating curve (recommended) Do not use 1.00-10.00 Do not use www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 30 User PARA Description Range / Explanation Setting Access Outdoor reset mode: The RS100 doesn’t use the Controller room temp for operation. Boiler supply temp is application displayed (pressing the dial displays room temp). type Room Control/RC Mode: Controller fully enabled...
  • Page 31 RS100 (in the room). NOTE: If the RS100 is set for outdoor reset mode (PARA 3=OFF or 1, PARA 4=OFF), a modem-driven switch can be placed in parallel with the outdoor sensor. When this switch closes, the RS100 will use this parameter to engage freeze protection.
  • Page 32 NOTE: If parameter 1 in the boiler is lower, it will override this setting; NOTE: This value will go to 203°F but the boiler will never eclipse 176°F; NOTE: 176°F=Default at shipment, 158°F=Default at System Reset -9 to 36°F Not for use with the RS100. Do not adjust 0°F 1 to 100 Do not adjust (temp) 5–240...
  • Page 33: Alarm Messages

    Time Date (Oct 19, (24 hour clock) 2010) Code Number (see boiler install manual for code explanations) Error codes 1 through 5; E0=Error code 1 is the most recent B0=Blocking code www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 34 Sensor Adjustment Chapter • Sensor adjustment allows an offset or calibration value to be applied to the RS100 • This is only accesible from the installer access level Factory User PARA Description Range / Explanation Setting Access RS100 internal temperature -9 to +9°F...
  • Page 35 Time Adjustment Chapter • Time adjustment allows date, day, and time for the RS100 • This is accesible from the user level (except Parameter 4) Factory User PARA Description Range / Explanation Setting Access Time 0:00 to 23:59 Year 2001 to 2099 01.01 to 31.12 (dd/mm) ;...
  • Page 36 BOILER PARAMETER SETTINGS THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER’S INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 37: Boiler Parameters

    Boiler Parameters (in relation to the RS100) • When using an RS100, the only adjustment that must be made at the boiler is PARA 73—most others can be made at the RS100 • Boiler parameter 2 or 14 may need to be set to establish an appropriate gradient control line (the defualt is 10°F/min)
  • Page 38 Boiler Parameters (in relation to the RS100) • When connecting an RS100, please observe the following notes at each parameter (continued): Parameter Chapter PARA Default Range Description RS100 Note 10°F/ Gradient acceleration—this is set when para 2 is This is not adjustable 28°F/min...
  • Page 39: Troubleshooting

    TROUBLESHOOTING THIS IS AN OVERVIEW ONLY—PLEASE REFER TO EACH BOILER OR CONTROLLER INSTALLATION MANUAL THAT IS SHIPPED WITH THE PRODUCT FOR THE MOST UP TO DATE INFORMATION. CONTACT RINNAI TECHNICAL SUPPORT IF NEEDED www.rinnai.us • © 2009 Rinnai America Corporation...
  • Page 40 • If the RS100 is set for RC, outside temperature will not influence the boiler except for freezing or summer setback conditions • If max temp at the boiler is lower than the max temp at the RS100, the boiler’s value will have precedence •...
  • Page 41 Thank You for being a part of Rinnai’s Product Expansion – RS100 Boiler Controller Training Program #501102A – 062311 www.rinnai.us • © 2009 Rinnai America Corporation...