Measured Values (Input Register) - Siemens SITRANS LR120 Modbus Operating Instructions Manual

Radar transmitters
Hide thumbs Also See for SITRANS LR120 Modbus:
Table of Contents

Advertisement

Technical data and dimensions
12.5 Measured values (Input Register)
Register
Number
3403
3600
3601
3602
12.5

Measured values (Input Register)

Register
Number
100
104
106
108
110
112
114
116
118
1300
1302
1304
52
Register Name
Data type Configurable Values
Max.-Adjustment
float32
r/w
Medium type
enum16
r/w
Application liquid
enum16
r/w
Application solid
enum16
r/w
Register Name
Data
type
Access
Status
enum8
ro
PV Unit
enum16
ro
PV
float32
ro
SV Unit
enum16
ro
SV
float32
ro
TV Unit
enum16
ro
TV
float32
ro
QV Unit
enum16
ro
QV
float32
ro
Status
enum8
ro
PV
float32
ro
SV
float32
0 ... Measurement
range
0=Liquids, 1=Solids
0 =Storage, 1= Process,
13=Wetwell, 8=Plastic,
9=Open, 12=Demo
0=Silo, 4= Bin/Hopper,
3=Open,12=Demo
Note
Bit 0: Invalid Measurement Value PV, Bit 1: Invalid
Measurement Value SV, Bit 2: Invalid Measurement
Value TV, Bit 3: Invalid Measurement Value QV
32=Degree Celsius, 33=Degree Fahrenheit,
39=Percent, 40=US Gallons, 41=Liters, 42=Imperial
Gallons, 43=Cubic Meters, 44=Feet, 45=Meters,
46=Barrels, 47=Inches, 48=Centimeters,
49=Millimeters, 111=Cubic Yards, 112=Cubic Feet,
113=Cubic Inches
Primary Variable in Byte Order CDAB
Unit Code
Secondary Variable in Byte Order CDAB
Unit Code
Third Variable in Byte Order CDAB
Unit Code
Quarternary Variable in Byte Order CDAB
See Register 100
Primary Variable in Byte Order of Register 3000
Secondary Variable in Byte Order of Register 3000
Operating Instructions, 10/2022, 62709-76-01, A5E49829030
Unit
Default
Value
-
Measurement
range
-
Liquids
-
Storage
-
Silo
SITRANS LR120 Modbus