(Optional) External Three-Breaker Maintenance Bypass (No Transformer)

The Three-Breaker MBS solution will allow the user to transfer the load between utility and inverter power sources without
interruption. It also allows the UPS itself to be isolated from utility power for safe maintenance or replacement of the unit.
When using an MBS, the utility and inverter waveforms must be identical so ONLY 240V input and output operation is
available for the 1600XPi in this configuration.
240V Wiring
The following connections must be made to the Utility Panel and the Load Panel. The Main UPS output is located on the
terminal block on the back of the UPS. (TB-4(X1) and TB-7(X3) 240 VAC.) Ensure the UPS voltage selector jumper is set
to 240 V.
UTILITY PANEL:
SINGLE Φ
240V
L1
L2
N
G
See the application instructions included with the External Maintenance Bypass Unit for wiring details.
Do NOT use two legs of a three phase, 208/120V utility to feed the 1600XPi, as shown
below, if this external maintenance bypass is being used. The output of the UPS and
the utility feed have different phase to neutral references and transfer between the two
could cause loss of power or damage to the load.
50
L1
X1
L2
X3
N
G
G
NOTICE
1600XPi Series UPS Installation and Operation Manual – 60616-014
MIB1
MIB2
L1
MBB1
L2
MBB2
UIB1
UIB3
UIB2
UIB4
N
G
MAIN OUTPUT
LOAD
PANEL
L1
L2
N
G

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents