This manual contains important instructions that should be followed during the installation and maintenance of the UPS and
its batteries.
Hardwired UPS units are not equipped with an over-current protection device nor an output disconnect for the AC output.
Circuit breakers should be provided by the user between the UPS Input and utility power, and the UPS output and the load
input. These devices should be rated as follows:
240VAC
RATING
Input
Breaker
Output
Breaker
* Ratings are for an 80% rated device.
The nominal battery voltages for these models are as follows:
BATTERY
VOLTAGE
Servicing of the batteries should only be performed by a qualified factory authorized representative who is knowledgeable
about batteries and the required precautions. Keep unauthorized personnel away from batteries. To arrange for battery
replacement, contact Toshiba Customer Support Center.
1. Turn off, lockout, and tagout all equipment before connecting the power wiring to the equipment or when performing
maintenance.
2. The maximum ambient operating temperature is 104 °F (40 °C).
3. Access panels should only be removed by authorized Toshiba field Service personnel.
4. UPS servicing should be performed by qualified Toshiba representatives only.
5. Battery servicing should be performed by qualified Toshiba representatives only.
6. Contact your Toshiba authorized service center for battery replacement.
6
3.6 kVA
5.2/6 kVA
30 A
50 A
20 A
35 A
3.6 kVA
5.2/6 kVA
144 Vdc
216 Vdc
288 Vdc
8 kVA
10 kVA
14 kVA
60 A
70 A
100 A
45 A
60 A
80 A
8 kVA
10 kVA
14 kVA
288 Vdc
288 Vdc
1600XPi Series UPS Installation and Operation Manual – 60616-014
18 kVA
22 kVA
100 A
125 A
100 A
125 A
18 kVA
22 kVA
288 Vdc
288 Vdc