Stop (Switch To Bypass) The Ups; Switch The Ups From Online To Maintenance Bypass - Toshiba 5000 SERIES Installation And Operation Manual

Nema-3r 3-phase ups. industrial duty 3-phase ups
Hide thumbs Also See for 5000 SERIES:
Table of Contents

Advertisement

2.
If the UPS is equipped with dual inputs, switch on the optional second Circuit Breaker. The breaker(s)
should normally remain in the ON position.
3.
If the UPS is equipped with an External Battery Cabinet, switch the cabinet breaker ON
4.
Verify that the AC Input LED on the front panel lights green. All LED's on the front panel may light for
a moment when the input breaker is turned on. This is normal. The UPS will now be supplying power
in the bypass mode.
When running the UPS for the first time or after the power failure backup
operation, charge the battery cabinet batteries, if any, for at least 24 hours
(input breaker on) before operating the connected load.
Using the UPS without charging the battery shortens the battery backup operation
time, which may result in the loss of data in case of a power failure.
5.
Press and hold, for 2 seconds, the RUN button on the touchscreen to begin UPS operation.
6.
Press the Quick View button on the Quick Access Toolbar and verify the UPS has input/output power.
If the UPS has backup batteries, verify the batteries are being charged.
13.3

Stop (Switch to Bypass) the UPS

To stop the UPS, press and hold, for 2 seconds, the STOP button on the touchscreen display. The On-Line
LED changes from green to off. The UPS is now in Bypass mode.
If the input breaker is turned off while UPS is in the bypass state, the output
power stops. Any load devices will lose power.
Ensure that all sensitive loads have been previously shut down.
To completely stop the UPS, open the input breaker MCCB, the secondary Input breaker (if available),
and the External Battery Cabinet breaker (if available).
13.4

Switch the UPS from Online to Maintenance Bypass

The UPS is equipped with a rotary maintenance bypass switch on the front of the Cable Bay. The access
to the switch is secured by a locking weather-proof panel.
To switch the UPS to Maintenance Bypass,
1. Open the weather-tight doors to the MBS and the Touchscreen. Press the touchscreen MAIN Tab.
2. Press the "STOP" icon on the touchscreen MAIN display. This sets the UPS in Bypass Mode. Output
power is now provided through the bypass circuit. While in this mode, if a power failure occurs
on the commercial power source, the UPS will loose power. Power to the critical load will be
interrupted. The battery charging circuit and chopper circuit remain active.
3. Verify the "ONLINE/FAULT" LED is OFF.
72
NOTICE
NOTICE
5000 Series NEMA-3R 3-Phase UPS Installation and Operation Manual – 92975-000