1600XP Series Single Phase Uninterruptible Power Systems
Product Specifications – Rev 5.0 October 2013
3.6kVA – 22kVA
1.0 Scope
This specification document describes the Toshiba 1600XP Series. The 1600XP is continuous
duty, single-phase, on-line, solid-state uninterruptible power supply system hereafter referred to
as the UPS. The UPS will supply a clean regulated AC power output sine wave which is
unaffected by the quality of the AC input. The input and output voltages are single phase.
2.0 General Operation
Under normal operating conditions, the UPS' rectifier converts alternating current AC power to
direct current (DC) power, which is required for the system's inverter and battery charger. The
charger supplies regulated DC power to keep the batteries constantly charged. The inverter uses
pulse width modulation (PWM) that fully utilizes the characteristics of insulated-gate bipolar
transistors (IGBT) to convert DC power to regulated AC power. Therefore there is a constant
supply of power. The batteries will instantaneously supply the inverter DC power when on AC
power line failure occurs.
2.1
Performance Standards
The UPS is designed in accordance with and is compliant with the following sections of the
current revisions of the following standards:
- ANSI C62.41 (IEEE 587) – Standard for Surge Withstand ability
- UL 1778 (CUL)
- CE
- FCC Class A
- National Electrical Code (NFPA-70)
- NEMA PE-1
- OSHA
- ASME
- ISO 9001, 14001
- RoHS
3.0
General
3.1
Materials
All materials used are of new manufacture using the latest technology and have not been in prior
service except for specified factory testing. IGBT's are used exclusively in the rectifier inverter
and chopper sections.
3.2
Components:
All functioning components are solid state with no moving parts.
The UPS consist of the following components:
A. Rectifier Converter
B. Chopper / Charger
C. Pulse-Width Modulated (PWM) Inverter
D. Static Switch Bypass

Advertisement

loading

Summary of Contents for Toshiba 1600XP

  • Page 1 3.6kVA – 22kVA 1.0 Scope This specification document describes the Toshiba 1600XP Series. The 1600XP is continuous duty, single-phase, on-line, solid-state uninterruptible power supply system hereafter referred to as the UPS. The UPS will supply a clean regulated AC power output sine wave which is unaffected by the quality of the AC input.
  • Page 2 1600XP Series Single Phase Uninterruptible Power Systems Product Specifications – Rev 5.0 October 2013 3.6kVA – 22kVA E. Microprocessor Controlled Logic and Touchpad Control Panel F. Input Circuit Breaker G. Battery System H. Output Isolation Transformer Assembly The UPS is delivered fully assembled and be fully functional.
  • Page 3 1600XP Series Single Phase Uninterruptible Power Systems Product Specifications – Rev 5.0 October 2013 3.6kVA – 22kVA interrupt the critical load. Transfer to Bypass may also be performed as a manual operation via the UPS touch screen front panel. E. POWER CONDITIONING MODE - Should the batteries be removed from the UPS, the UPS continues to function and still provide protection against spikes, common/normal mode noise, load steps and frequency shifts (without battery back-up capability).
  • Page 4 1600XP Series Single Phase Uninterruptible Power Systems Product Specifications – Rev 5.0 October 2013 3.6kVA – 22kVA 4.3.3 Static Bypass Switch 1) TRANSFER - The static bypass switch consists of thyristor switches in conjunction with an output contactor to permit manual switching from bypass to UPS and UPS to bypass without power interruption.
  • Page 5 1600XP Series Single Phase Uninterruptible Power Systems Product Specifications – Rev 5.0 October 2013 3.6kVA – 22kVA Frequency Range : 45 - 65 Hz Power Factor : > 0.95 lagging Input Capacity : 110% of UPS Output Capacity Input Current Limit...
  • Page 6 1600XP Series Single Phase Uninterruptible Power Systems Product Specifications – Rev 5.0 October 2013 3.6kVA – 22kVA 5.3 Environmental Heat Generation : UNIT BTU/hr. 3.6kVA 2139 6 kVA 3564 8 kVA 4095 10 kVA 5118 14 kVA 6610 18 kVA...
  • Page 7 1600XP Series Single Phase Uninterruptible Power Systems Product Specifications – Rev 5.0 October 2013 3.6kVA – 22kVA 7.0 System Status and Control Indicators Front Panel The UPS has a front touch screen panel that shows all of its parameters while allowing control of the UPS.
  • Page 8 DB9 Dry Contacts This is a standard feature that is offered on all the 1600XP models. This feature has a limited amount of status that can be monitored remotely, but it stills offers the most vital alarms and faults signals.
  • Page 9 The matching battery cabinet comes with a DC breaker and a Anderson Style Connector cable for easy setup. Up to two matching battery cabinets can be combined with the 1600XP. Here are the battery runtimes when combined with one or two battery cabinets:...

This manual is also suitable for:

1600xp series