Toshiba 1600XPi Series Installation And Operation Manual page 86

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

Unit (Capacity)
Inverter Overload Capacity
Bypass Overload Capacity
Crest Factor
Environment
Operating Temperature
59 – 77 °F (15 – 25 °C) Recommended
Storage Temperature
Installation Area
Operating Humidity
Altitude
Acoustical Noise
Heat Generation (Typical)
Operation Diagnosis
Battery Check
Input OV Protection
Battery Lifetime
Internal Temperature
Event Data Storage Registers
Applications
Switches
Bypass Switch
Bypass Disable
Automatic Retransfer
Interface/Communications
Real Time Clock
Schedule Operation
Autostart
Remote ON/OFF
Emergency Power Off
LED Display
Operator Interface
1.
Input/output figures rated for 240 volts unless otherwise stated. Output ratings given for 0.85PF are only valid when
the input voltage is greater than 204 volts; otherwise, ratings given for 0.70PF are applicable.
2.
At 6600 ft (2000 m) above sea level, output capacity should be derated by 3% per additional thousand feet elevation.
A8
NON–STANDARD MODELS: 5.2 KVA (CONT'D)
To be installed in a well ventilated area free of airborne dust,
metal particles or flammable gas, allow at least 4 inches on all sides
50 dB (A) maximum @ 1 meter from front panel
Performed on start up, by schedule, on-demand (user configurable)
based upon battery ambient temperature (LCD display, LED and beeps)
UPS gives indication of internal temperature, alarm when high temp
32 – Operation, 32 – Backup, 32
Static switch < ¼ cycle (50 Hz – 5 ms/60 Hz – 4.16 ms)
Factory or authorized service center selectable only
Real Time Clock with backup Lithium Ion Battery
Schedule ON/OFF operation of UPS using RemotEye 4 communication software
Automatic UPS Startup when AC is applied – Option can be enabled or disabled at user's
3 LED's indicating On-Line/Fault, Warning, and A/C Input
1600XPi Series UPS Installation and Operation Manual – 60616-014
5.2kVA (4.4 kW)
125% for 30 sec./150% for 10 sec.
125% for 10 min./1000% for 1 cycle
3.0
60 Hz 32 – 104 °F (0 – 40 °C)
50 Hz 32 – 91 °F (0 – 33 °C)
-4 – 104 °F (-20 – 40 °C)
30 – 90% non-condensing
< 6600 ft. (2000 m) above sea level
3089 BTU/Hr
Standard
UPS calculates battery replacement time
Warnings, 32 – Faults, 32
Generator compatible
discretion
Standard – External terminal
Standard – Terminal contacts only
Interactive Touchscreen
1
2
Test, 32