Communication Interfaces; Remote Contacts - Toshiba 1600XPi Series Installation And Operation Manual

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

18

Communication Interfaces

18.1

Remote Contacts

The remote contacts interface is provided as a set of solid state switching devices. The switches are available through a
DB9 male connector on the rear of the UPS. The following chart shows the pin assignment for each signal.
MAXIMUM CURRENT CARRYING CAPACITY
Voltage
48 Vdc peak
30 Vac rms
(42 Vac peak)
Pin
Signal Function
1
Fault Signal
2
UPS stop common
3
UPS stop signal input
4
Normal input power supply
5
Signal common
6
Bypass operation
7
Battery voltage drop
8
UPS operation
9
Power failure signal
NOTE:
Pin switches are shown in their inactive states. For example, if battery voltage is low, pin 7 will be connected to pin 5.
1:
When not applying +3 to +15V, the voltage supplied to pins 2 and 3 should be reverse biased (-3 to -15V) to avoid
unintentional closure due to signal noise.
44
OF THE SWITCH
Current
70 mA peak
50 mA rms
(70 mA peak)
Closed when fault detected (See
Section 24.3 for list of applicable
faults)
Backup stop when +3 to +15 V
applied between pins 2 and 3.
Closed with normal supply power
Common signal return
Closed during bypass operation
If UPS detects battery voltage
less than Low Battery Threshold
(Parameter 547), UPS will output
logic high to pin
Closed during inverter operation
Closed at power failure
DB9 MALE CONNECTOR OUTLINE
(FACING CONNECTOR)
Logic
1
1600XPi Series UPS Installation and Operation Manual – 60616-014