Optional Bypass Fuse Location; Installation Procedure; Figure.2 Front View Of G9000 Ups With The Door And The Access Panel Open - Toshiba G9000 Series Installation Manual

Optional bypass fuse, 480/480 v 1000 kva
Hide thumbs Also See for G9000 Series:
Table of Contents

Advertisement

3

OPTIONAL BYPASS FUSE LOCATION

Figure.2 Front view of G9000 UPS with the door and the access panel open

4

INSTALLATION PROCEDURE

Step 1: Turn off the critical load.
Step 2: Turn off the UPS.
Step 3: Remove all power from the UPS. (Open all MCCBs connected to the UPS.)
Step 4: Wait five minutes after removing power from the UPS before opening access panels.
Step 5: Open the door of bypass cabinet and the access panel.
G9000 1000kVA OPTIONAL BYPASS FUSE Installation Guide – 92932-001
52SU
52SV
52SW
Shock Hazard
Remove all power from the UPS before opening access panels.
Verify power/energy is not present in the UPS.