24.2
Cleaning the Touchscreen
The touchscreen display is covered with a protective Teflon coating. It should be cleaned with a clean, damp cotton cloth
to avoid scratching the coating.
24.3
Battery Pack Replacement
The 1600XPi come equipped with a set of internal backup batteries packaged in sets of 6 batteries per battery pack. The
two battery packs, P/N 51896, and P/N 60995 are outwardly similar but distinctly different.
Ensure the 1600XPi battery packs are replaced with battery packs of the same part
number. Failure to do so may cause unexpected loss of backup power.
Battery Tray Plug for:
3.6, 5.2, 6, 8, 14, and 18 kVA
P/N 51896-FS
Battery Tray Plug for:
10 and 22 kVA
P/N 60995-FS
(Dual conductors because
of higher battery pack dis-
charge current)
62
NOTICE
1600XPI BATTERY TRAY PLUG DIFFERENCES
1600XPi Series UPS Installation and Operation Manual – 60616-014