System Mode Messages

A UPS Mode message is generated when the UPS changes operating mode. The following tables list the possible operat-
ing modes for the UPS.
Display
Backup
BattTest
Bypass
On–Line
Shutdown
Startup
23.6

System Status Messages

A UPS Status message is generated when the UPS changes its status (from inverter to bypass mode, for example). The
table below shows the possible Status messages and their meaning.
Display
BYP
CHRGERR
DLYST
EE1ST
EE2RAERR
EEUPERR
60
Meaning
Overload – UPS is overloaded
(110% and above) Unit will switch
to bypass operation or shut down
if no action is taken.
Communication Error between
RemotEye and UPS.
Communication Error at Service
Port.
Communication Error at LAN.
DC Bus Undervoltage During Bat-
tery Test.
Input Overvoltage – Input voltage
exceeds UPS specifications.
Input Undervoltage – Input voltage
less than UPS specifications.
Backup – Power comes from other than input.
Battery Test – Battery test in progress.
Bypass – UPS is offline, power is being provided directly from UPS input.
On-Line – Input converter and inverter are running (Double conversion mode).
Shutdown – No output, DC Bus is charged through Softstart Resistor.
Startup – UPS is starting up.
Meaning
Bypass mode – Power is supplied by UPS input.
Charger Error – Charger overvoltage error.
Delay Start – UPS is counting down prior to
startup.
EEPROM is loaded with default values.
EEPROM to RAM loading Error.
EEPROM updating Error.
Shut down excess equipment to reduce load.
Ensure RemotEye is connected to UPS. Call
Toshiba for service.
Call Toshiba for service.
Call Toshiba for service.
Call Toshiba for service.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Voltage returns to normal. Check
bypass power.
UPS in On-Line Mode: UPS switches to BACKUP
mode until Input Voltage returns to normal. Check
bypass power.
Meaning
No action needed.
Call Toshiba for service.
No action needed.
No action needed.
Call Toshiba for service.
Call Toshiba for service.
1600XPi Series UPS Installation and Operation Manual – 60616-014