Ups Lan Shutdown Signal Operation; Rs-232C - Toshiba 1600XPi Series Installation And Operation Manual

Single phase - 3.6/5.2/6/8/10/14/18/22 kva
Hide thumbs Also See for 1600XPi Series:
Table of Contents

Advertisement

18.2

UPS LAN Shutdown Signal Operation

When the UPS stop signal is sent to the UPS through pin 2 and 3 of the external contact interface, it is possible to
automatically reset the following operating systems (OS), which can automatically implement the shutdown function and
restart the operation: Windows NT, IBM OS/2 LAN server, LANtastic
Parameter 646 – UPS Shutdown by LAN Input Signal Enabled/Disabled
Parameter 647 – UPS Shutdown by LAN Signal Permitted Time Window (Adjustable)
With the UPS Shutdown by LAN Signal function enabled, when line power fails and the UPS goes to backup the LAN will
shutdown even if the UPS returns to normal mode during the shutdown process.
LAN shutdown can take several minutes. The UPS Shutdown by LAN Signal function has a companion UPS Shutdown
by LAN Signal Permitted Time Window parameter that can be set to allow sufficient time to complete the LAN shutdown
process (default: 10 minutes) even if line power is restored during LAN shutdown.
LAN shutdown is treated as a restart after battery shutdown. The restart of the LAN will be determined by the Restart After
Battery Shutdown timer.
Connect only the UPS stop signal to the external contact interface for automatic processing so that the UPS output will not
be turned off by mistake.
If the computer is started/restarted within 10 minutes after the recovery from a power failure, the power supply may
be reset while the computer is restarting.
18.3

RS-232C

The RS232C port can be used by authorized service personnel. The port is provided using a DB9 female connector located
on the rear of the UPS. For reference, the pinout of the connector is illustrated below.
RS-232C CONNECTOR PIN ASSIGNMENT
Pin
I/O
Symbol
1
This pin is not used
2
Input
RXD
3
Output
TXD
4
Output
DTR
5
-
SG
6
Input
DSR
7
Output
RTS
8
Input
CTS
9
This pin is not used
1600XPi Series UPS Installation and Operation Manual – 60616-014
Description
Receive data
Transmit data
Data terminal ready
Signal ground
Data set ready
Request to send
Clear to send
DB9 FEMALE CONNECTOR OUTLINE
(FACING CONNECTOR)
45