Operating The High-Spec Wired Remote Controller; How To Set The External Static Pressure - Panasonic Inverter R32 Series Technical Data & Service Manual

Table of Contents

Advertisement

1
1-7-2. Operating the High-spec Wired Remote
Controller (CZ-RTC5A / CZ-RTC5B)
[

How to set the external static pressure

1. Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD
display.
2. Press the
If you wish to see the next screen instantly, press the
or
Select "8. Detailed settings" on the LCD display and press
the
button.
The "Detailed settings" screen appears on the LCD display.
Select the "Unit no." by pressing the
button for changes.
20:30 (THU)
]
START
,
and
or
button to see each menu.
button.
or
3. Select the "Code no." by pressing the
button.
Change the "Code no." to "B0" by pressing the
4. Select the "Set data" by pressing the
button.
Select one of the "Set data" among "0001" – "0015"
according to the desired external static pressure setting by
pressing the
Then press the
(See the table below.)
When setting to auto airflow volume control:
buttons
Select the setting data to "-002".
Then press the
Table 1-7-2 Setting the external static pressure
60, 71
External static pressure of the rated
airflow volume (Pa)
150
140
130
120
100
70
60
50
30
10
No auto airflow volume setting
Auto airflow volume setting
5. Select the "Unit no." by pressing the
button and press the
The "Exit detailed settings and restart?" (Detailed setting-
end) screen appears on the LCD display.
Select "YES" and press the
When the setting is completed, perform the test run for the
external static pressure setting described in "Auto External
Static Pressure Setting Operation".
1-7-4
button (or keeping it pressed).
or
button.
button.
button.
Indoor unit type
100, 125, 140
150
140
130
120
110
100
70
50
30
10
button.
button.
or
or
or
Item code
B0
0015
0014
0013
0012
0011
0008
0006
0005
0003
0001
-001
-002
or