CHECK OF DENSITY LIMIT

The refrigerant (R32), which is used in the air conditioner, is a flammable refrigerant. So the requirements for installation space of
appliance are determined according to the refrigerant charge amount [m
The minimum indoor floor space compared with the amount of refrigerant is roughly as follows:
[Type U2, E1, T2, F1]
20.0
18.0
16.0
14.0
12.0
10.0
8.0
6.0
4.0
2.0
0.0
0
0.5
[Type K2]
35.0
32.5
30.0
27.5
25.0
22.5
20.0
17.5
15.0
12.5
10.0
7.5
5.0
2.5
0.0
0.0
0.5
[m
]
: The refrigerant charge amount (Total of refrigerant at shipment and refrigerant charge amount in the field).
c
[m
] : Maximum refrigerant charge amount
max
[m
]
max
] ≤ 1.22
[m
: Can be installed
c
] ≤ [m
1.22 < [m
] : Installation possible with in the range of slanted line part
max
c
[m
] > [m
]
: Can not be installed
max
c
Can be installed
1
1.5
2
2.5
[m
] : the refrigerant
c
charge amount (
1
2 .
2
1
8 .
0
Can be installed
1.0
1.5
2.0
2.5
[m
] : the refrigerant
c
charge amount (kg)
1.22
U-60PZ2R5
U-100PZ2R5
U-71PZ2R5
U-100PZ2R8
1.80
3.50
] used in the appliance.
c
* U-60PZ2R5, U-71PZ2R5,
U-100PZ2R5, U-100PZ2R8
Can not be installed
* U-60PZ2R5, U-71PZ2R5
Can not be installed
Can not be installed
3
3.5
4
4.5
kg
)
3
5 .
0
3
8 .
8
* U-100PZ2R5, U-100PZ2R8
Can not be installed
Can not be installed
3.0
3.5
4.0
4.5
3.50
3.88
U-125PZ2R5
U-125PZ2R8
3.88
v
5
5.0
U-140PZ2R5
U-140PZ2R8
3.88