Panasonic Inverter R32 Series Technical Data & Service Manual page 103

Table of Contents

Advertisement

1
(B) When an obstruction is present on the air outlet side
(B) When an obstruction is present on the air outlet side
● When the upward area is open
● When the upward area is open
(1) One outdoor unit installed individually
(1) One outdoor unit installed individually
* When also using the air-discharge chamber, provide a space of
* When also using the air-discharge chamber, provide a space of
500 mm or more.
500 mm or more.
● When an obstruction is present also in the upward area
● When an obstruction is present also in the upward area
(1) One outdoor unit installed individually
(1) One outdoor unit installed individually
b
(C) When an obstruction is present on both the air inlet and air outlet sides
(C) When an obstruction is present on both the air inlet and air outlet sides
Case 1: When an obstruction on the air outlet side is higher than the outdoor unit (L > H)
Case 1: When an obstruction on the air outlet side is higher than the outdoor unit (L > H)
(There is no height restriction on the air inlet side.)
(There is no height restriction on the air inlet side.)
● When the upward area is open
● When the upward area is open
(1) One outdoor unit installed individually
(1) One outdoor unit installed individually
L
* When using the air-discharge chamber, provide a space of 300 mm
* When using the air-discharge chamber, provide a space of 300 mm
or more.
or more.
● When an obstruction is present also in the upward area (Do not use the air-discharge chamber.)
● When an obstruction is present also in the upward area (Do not use the air-discharge chamber.)
(1) One outdoor unit installed individually
(1) One outdoor unit installed individually
b
H
a 500 mm or more
a 500 mm or more
*
a 500 mm or more
a 500 mm or more
b 500 mm or less
b 500 mm or less
c 300 mm or more
c 300 mm or more
c
a 100 mm or more
a 100 mm or more
H
b 500 mm or more
b 500 mm or more
*
a 200 mm or more
a 200 mm or more
b 500 mm or less
b 500 mm or less
c
c 1,000 mm or more
c 1,000 mm or more
L
(2) Two or more units installed side by side
(2) Two or more units installed side by side
(2) Two or more units installed side by side
(2) Two or more units installed side by side
(2) Two or more units installed side by side
(2) Two or more units installed side by side
L
The dimensional relationship between H, A, and L is as
The dimensional relationship between H, A, and L is as
shown in the following table.
shown in the following table.
L
L
0 < L ≤ 1/2H
0 < L ≤ 1/2H
L ≤ H
L ≤ H
1/2H < L ≤ H
1/2H < L ≤ H
Install the frame to achieve L ≤ H.
Install the frame to achieve L ≤ H.
H < L
H < L
Close the area under the frame so that the outlet air does
Close the area under the frame so that the outlet air does
not bypass there.
not bypass there.
1-11-2
a 1,000 mm or more
a 1,000 mm or more
b 250 mm or more
b 250 mm or more
c 250 mm or more
c 250 mm or more
d
a 500 mm or more
a 500 mm or more
b 250 mm or more
b 250 mm or more
c 250 mm or more
c 250 mm or more
e
d 500 mm or less
d 500 mm or less
e 1,000 mm or more
e 1,000 mm or more
a 200 mm or more
a 200 mm or more
b 1,000 mm or more
b 1,000 mm or more
c 250 mm or more
c 250 mm or more
d 250 mm or more
d 250 mm or more
H
Unit: mm
Unit: mm
A
A
300
300
500
500