Auto Address Setting Using The Remote Controller - Panasonic Inverter R32 Series Technical Data & Service Manual

Table of Contents

Advertisement

2-8. Auto address setting using the remote controller

High-spec Wired Remote Controller (CZ-RTC5A / CZ-RTC5B)
(1) Keep pressing the
simultaneously for 4 or more seconds.
The "Maintenance func" screen appears on the LCD
display.
(2) Press the
or
If you wish to see the next screen instantly, press the
or
button.
Select "9. Auto address" on the LCD display and press the
button.
Maintenance func
9. Auto address
10. Set elec. consumption
11. Set touch key
12. Check touch key
Sel.
Page [
(3) The "Auto address" screen appears on the LCD display.
Change the "Code no." to "A1" by pressing the
button.
Auto address
Code no.
A1
Sel.
Next
Timer remote controller (CZ-RTC4)
Auto address setting in Cooling mode cannot be done from the remote controller.
NOTE
● Selecting each refrigerant system individually for auto address setting
● Auto address setting for each system
: Item code "A1"
(1) Press the remote controller timer time
button at the same time.
(Press and hold for 4 seconds or longer.)
(2) Next, press either the temperature setting
(Check that the item code is "A1".)
(3) Use either the
button to set the system No. to perform auto
address setting.
(4) Then press the
button.
(Auto address setting for one refrigerant system begins.) (When
auto address setting for one system is completed, the system
returns to normal stopped status.)
<Approximately 4 – 5 minutes is required.>
(During auto address setting, "
remote controller.
This message disappears when auto address setting is
completed.)
(5) Repeat the same steps to perform auto address setting for each
successive system.
,
and
buttons
button to see each menu.
20:30 (THU)
] Confirm
or
20:30 (THU)
O/D unit no.
1
button and
button.
/
" is displayed on the
[
]
START
(4) Select the "O/D unit no." by pressing the
button.
Select one of the "O/D unit no." for auto address by
pressing the
Approximately about 10 minutes are required.
When auto address setting is completed, the units return to
normal stopped status.
(2)
(1)
2-7
20:30 (THU)
or
or
button.
(4)
2
(4)
(3)