1-2. Dimensional Data

Dimensional Data
(A) Indoor Units: 4-Way Cassette Type S-100PU2E5B / 125PU2E5B / 140PU2E5B
Indoor Units: S-100PU2E5A / S-125PU2E5A / S-140PE2U5A
840
480
2
7
Less than 35
Less than 300
Raise dimension of drain tube
The length of the suspension bolts
should be selected so that there is
a gap of 30 mm or more below the
lower surface of the ceiling (18 mm
or more below the lower surface of
the main unit), as shown in the
figure at right. If the suspension
bolt is too long, it will contact
the ceiling panel and the unit
cannot be installed.
1
Air intake
2
Discharge outlet
3
Refrigerant tubing (liquid tube) ø9.52 (flared)
4
Refrigerant tubing (gas tube) ø15.88 (flared)
5
Drain tube connection port VP25 (outer dia. ø32)
6
Power supply port
7
Discharge duct connection port (ø150)
8
Suspension bolt hole (4-12×30 elongated hole)
9
Fresh air intake duct connection port (ø100) *
ECONAVI sensor (Only CZ-KPU3A)
10
* Necessary to attach duct connecting flange(field supplyed).
<Filter dimension>
520 x 520 x 15
(Ceiling opening dimensions)
(Suspension bolt pitch)
8
5
340
110
7
Less than 35
2
515
10
2
1
2
X
860~910
XX
780
3
4
840
272
51
6
950
(Air intake)
2
1-2-2
1-
unit: mm
Y
7
2
7
9
480
View X
Z
35
View XX
4 - M4
105
Tapping screw holes
115
Detailed view Y
64
4 - M4
80
Tapping screw holes
Detailed view Z
1