Auto Address Setting - Panasonic U-8ME2E8 Service Manual & Test Run Service Manual

2way system, r410a
Table of Contents

Advertisement

4. Auto Address Setting

4. Auto Address Setting
Example: Basic Wiring Diagram (1)
• Case of no link wiring
(Inter-unit control wiring is not connected to a multiple system.)
Indoor unit address setting is possible without starting the compressor.
Unit 1 setting (outdoor main unit)
System address
(System 1 setting)
(SW1)
(SW2)
ON
1
2
Number
(SW6)
of outdoor
ON
units (3 units
setting)
1
Outdoor Unit
Indoor unit
Remote controller
Case 1
Auto Address Control from Outdoor Unit
1. Regarding the number of outdoor units, set the Dip switch (SW6) for setting the number of outdoor units on Unit 1 control P.C.B to 3
ON
ON
units
and the Unit Number Setting Dip switch (SW5) to unit number 1.
1
2
3
OFF
This unit becomes the outdoor main unit.
2. Set the Unit Number Setting switch (SW5) on unit 2 control P.C. board to unit number 2.
Set the Unit Number Setting switch (SW5) on unit 3 control P.C. board to unit number 3.
3. Check the refrigerant system's Address Setting Rotary switch (SW1) on outdoor main unit control P.C. board to "1" and the Dip switch
(SW2) to "0" (at shipment).
4. Regarding the setting of the number of indoor units connected to the outdoor unit, set the Dip switch (SW4) for setting the number of
indoor units on outdoor main unit control P.C. board connected to the outdoor unit to "1".
If the Rotary switch (SW3) set to "0", 10 units can be prepared for operation.
5. Turn on power to indoor and outdoor units.
6. Short circuit the A.ADD pin (CN30) on outdoor main unit control P.C. board for over 1 second long and open circuit.
Communication for auto address setting begins.
* To cancel, short circuit the A.ADD pin (CN30) again for over 1 second long and then open circuit. The LED that
indicates auto address setting goes out and the process is stopped.
Be sure to perform auto address setting again.
Auto address setting is completed when LEDs 1 and 2 on outdoor main unit control P.C. board go out.
7. Remote control operation is now available.
* When auto address setting is controlled by the remote controller, perform auto address setting by the remote controller after step 5
described above.
* It is not necessary to control the terminating
No. of indoor units
(10 units setting)
(SW3)
0
ON
(SW4)
ON
ON
OFF
1
2
3
OFF
Unit
Unit
(SW5)
number
number
ON
ON
ON
setting
setting
(unit 2)
2
3
OFF
(unit 1)
1
2
3
OFF
Set the terminating
resistance pin
to SHORT side.
Unit 1
(CN67)
(Main)
Inter-outdoor unit
control wiring
Inter-unit control wiring
1-1
1-2
ON
ON
1
2
OFF
resistance pin (3P) (CN67) on the outdoor
unit P.C. board.
3P pin is plugged in SHORT side at shipment.
Confirm it is plugged in SHORT side.
Unit 2 setting
(SW5)
Unit
ON
ON
number
setting
1
2
3
OFF
(unit 3)
Unit 2
(Sub)
Inter-outdoor unit
control wiring
1-3
Remote control
communication wiring
ON
1
ON
ON
ON
7-7
2WAY SYSTEM
3P terminating
resistance pin
(SHORT side)
SHORT
Unit 3 setting
(SW5)
ON
ON
1
2
3
OFF
Unit 3
(Sub)
1-10
2
3
1
2
3
1
2
3
ON
1
2
3
OFF
Test Run
OPEN
7