York MILLENNIUM YCAR0315 Installation Operation & Maintenance page 130

Air-cooled reciprocating liquid chillers
Table of Contents

Advertisement

Micro Panel
L E A V I N G
L I Q U I D
C U T O U T
=
This display shows the Low Leaving Chilled Liquid
Cutout programmed at the time of the fault.
H I G H
M O T O R
U N L O A D
-
1 0 0 %
This message shows the programmed %FLA Motor
Current Unload at the time of the fault.
L O C A L / R E M O T E
L O C A L
This message shows whether remote or local commu-
nications was selected at the time of the fault.
L E A D / L A G
C O N T R O L
A U T O M A T I C
This message displays the lead/lag selection programmed
at the time of the fault.
L C H L T
=
4 2 . 3
R C H L T
=
4 8 . 9
This message indicates the leaving and return chilled
liquid temperature at the time of the fault.
M C H L T
=
4 3 . 0
This message indicates the mixed water temperature at
the time of the fault. A mixed water sensor may be
present when multi-unit sequencing is utilized. If no
mixed water temperature sensor is installed, the display
will not appear.
S E T P O I N T
R A N G E
=
+ / -
This message displays the programmed chilled liquid
setpoint and deviation (control range) programmed at
the time of the fault.
A M B I E N T
=
7 2 . 6 ° F
This message indicates the outdoor Ambient Air Tem-
perature at the time of the fault.
130
T E M P
3 4 . 0 ° F
C U R R E N T
F L A
M O D E
° F
° F
° F
=
4 2 . 0 ° F
2 . 0 ° F
A I R
T E M P
L E A D
S Y S T E M
S Y S T E M
N U M B E R
This message indicates which system was in the lead at
the time of the fault.
E V A P
P U M P
E V A P
H E A T E R
This message indicates the status of both the evapora-
tor pump signal from the microprocessor and the evapo-
rator heater.
A C T I V E
R E M O T E
N O N E
This message indicates that a remote device such as a
Remote Control Center, an ISN controller, or another
device sending a PWM signal for temperature or cur-
rent temperature or current reset is overriding control
points programmed through the keypad or default mi-
croprocessor setpoints.
System Data:
Following the Common Data is a sequence of twenty
information displays which are given twice, first for
System 1, then for System 2. In each example, "#" is
used to indicate System number.
S Y S
#
C O M P R E S S O R
I S
This message indicates whether the compressor on this
system was ON or OFF at the time of the fault.
S Y S
#
R U N
1 - 3 - 4 8 - 1 7
This message shows the Run Time logged on the sys-
tem since the last compressor start, in Days (D), Hours
(H), Minutes (M), and Seconds (S).
S Y S
#
M O T O R
2 5 5
A M P S
=
This message indicates the compressor motor current
in as a percentage of Full Load Amps.
FORM 150.52-NM2 (1001)
I S
1
I S
O N
I S
O F F
C T R L
O N
T I M E
D - H - M - S
C U R R E N T
8 2 %
F L A
YORK INTERNATIONAL