Table 3 - Condenser Fan Control And Fan Contactor Data For Dxrt Units With 3 Fans / System; Table 4 - Condenser Fan Control And Fan Contactor Data For Dxrt Units With 4 Fans / System; Table 5 - Condenser Fan Control And Fan Contactor Data For Dxrt Units With 5 Fans / System - York MILLENNIUM YCAR0315 Installation Operation & Maintenance

Air-cooled reciprocating liquid chillers
Table of Contents

Advertisement

TABLE 3 – CONDENSER FAN CONTROL AND FAN CONTACTOR DATA FOR DXRT UNITS WITH
3 FANS/SYSTEM (YCAR 0315, 0345, 0365 AND 0385)
Fan
Fans
Stage
1
1
S
2
3
Y
3
5
S
4
1, 5
5
3, 5
1
6
1, 3, 5
1
2
S
2
4
Y
3
6
S
4
2, 6
5
4, 6
2
6
2, 4, 6
TABLE 4 – CONDENSER FAN CONTROL and FAN CONTACTOR DATA FOR DXRT UNITS WITH
4 FANS/SYSTEM (YCAR 0415, 0435, 0485 AND 0525)
Fan
Fans
Stage
1
1
S
2
3
Y
3
5, 7
S
4
1, 5, 7
5
3, 5, 7
1
6
1, 3, 5, 7
1
2
S
2
4
Y
3
6, 8
S
4
2, 6, 8
5
4, 6, 8
2
6
2, 4, 6, 8
TABLE 5 – CONDENSER FAN CONTROL and FAN CONTACTOR DATA FOR DXRT UNITS WITH
5 FANS/SYSTEM (YCAR 0575, 0645 AND 0685)
Fan
Fans
Stage
1
1
S
2
3, 5
Y
3
7, 9
S
4
1, 7, 9
5
3, 5, 7, 9
1
6
1, 3, 5, 7, 9
1
2
S
2
4, 6
Y
3
8, 10
S
4
2, 8, 10
5
4, 6, 8, 10
2
6
2, 4, 6, 8, 10
YORK INTERNATIONAL
ON
OFF
Conditions
Conditions
DP
DP and OAT
>15.2 BAR
<10.3 BAR and <15.6°C
>16.2 BAR
<11.4 BAR and <18.3°C
>17.2 BAR
<12.4 BAR and <21.1°C
>18.3 BAR
<13.4 BAR and <23.9°C
>19.3 BAR
<14.5 BAR and <26.7°C
>20.0 BAR
<15.2 BAR and <29.4°C
>15.2 BAR
<10.3 BAR and <15.6°C
>16.2 BAR
<11.4 BAR and <18.3°C
>17.2 BAR
<12.4 BAR and <21.1°C
>18.3 BAR
<13.4 BAR and <23.9°C
>19.3 BAR
<14.5 BAR and <26.7°C
>20.0 BAR
<15.2 BAR and <29.4°C
ON
OFF
Conditions
Conditions
DP
DP and OAT
>15.2 BAR
<10.3 BAR and <15.6°C
>16.2 BAR
<11.4 BAR and <18.3°C
>17.2 BAR
<12.4 BAR and <21.1°C
>18.3 BAR
<13.4 BAR and <23.9°C
>19.3 BAR
<14.5 BAR and <26.7°C
>20.0 BAR
<15.2 BAR and <29.4°C
>15.2 BAR
<10.3 BAR and <15.6°C
>16.2 BAR
<11.4 BAR and <18.3°C
>17.2 BAR
<12.4 BAR and <21.1°C
>18.3 BAR
<13.4 BAR and <23.9°C
>19.3 BAR
<14.5 BAR and <26.7°C
>20.0 BAR
<15.2 BAR and <29.4°C
ON
OFF
Conditions
Conditions
DP
DP and OAT
>15.2 BAR
<10.3 BAR and <15.6°C
>16.2 BAR
<11.4 BAR and <18.3°C
>17.2 BAR
<12.4 BAR and <21.1°C
>18.3 BAR
<13.4 BAR and <23.9°C
>19.3 BAR
<14.5 BAR and <26.7°C
>20.0 BAR
<15.2 BAR and <29.4°C 9M, 10M, 11M, 12M, 13M
>15.2 BAR
<10.3 BAR and <15.6°C
>16.2 BAR
<11.4 BAR and <18.3°C
>17.2 BAR
<12.4 BAR and <21.1°C
>18.3 BAR
<13.4 BAR and <23.9°C
>19.3 BAR
<14.5 BAR and <26.7°C
>20.0 BAR
<15.2 BAR and <29.4°C 15M, 16M, 17M, 18M, 19M
FORM 150.52-NM2 (1001)
Fan
Wire
Contactor
Number
9M
130
10M
131
11M
132
9M, 11M
130, 132
10M, 11M
131, 132
9M, 10M, 11M
130, 131, 132
15M
230
16M
231
17M
232
15M, 17M
230, 232
16M, 17M
231, 232
15M, 16M, 17M
230, 231, 232
Fan
Wire
Contactor
Number
9M
130
10M
131
11M, 12M
132
9M, 11M, 12M
130, 132
10M, 11M, 12M
131, 132
9M, 10M, 11M, 12M
130, 131, 132
15M
230
16M
231
17M, 18M
232
15M, 17M, 18M
230, 232
16M, 17M, 18M
231, 232
15M, 16M, 17M, 18M
230, 231, 232
Fan
Wire
Contactor
Number
9M
130
10M, 11M
131
12M, 13M
132
9M, 12M, 13M
130, 132
10M, 11M, 12M, 13M
131, 132
130, 131, 132
15M
230
16M, 17M
231
18M, 19M
232
15M, 18M, 19M
230, 232
16M, 17M, 18M, 19M
231, 232
230, 231, 232
Relay
Board
Output
15
14
10
10,15
10, 14
10, 14, 15
15
14
10
10,15
10, 14
10, 14, 15
Relay
Board
Output
15
14
10
10,15
10, 14
10, 14, 15
15
14
10
10,15
10, 14
10, 14, 15
Relay
Board
Output
15
14
10
10,15
10, 14
9
10, 14, 15
15
14
10
10,15
10, 14
10, 14, 15
149