York MILLENNIUM YCAR0315 Installation Operation & Maintenance page 132

Air-cooled reciprocating liquid chillers
Table of Contents

Advertisement

Micro Panel
SAMPLE PRINTOUT OF FAULT HISTORY DATA
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
SAFETY SHUTDOWN NUMBER 1
SHUTDOWN @ 3:56 PM 28 AUG 00
SYS 1 HIGH DSCH PRESS SHUTDOWN
SYS 2
NO FAU.L.TS
OPTIONS
CHILLED LIQUID
AMBIENT CONTROL
REFRIGERANT TYPE
PROGRAM VALUES
DSCH PRESS CUTOUT
DSCH PRESS UNLOAD
SUCT PRESS CUTOUT
HIGH AMBIENT CUTOUT
LOW AMBIENT CUTOUT
LEAVING LIQUID CUTOUT
MOTOR CURRENT UNLOAD
ANTI RECYCLE TIME
LOCAL/REMOTE MODE
LEAD /LAG CONTROL
UNIT DATA
LEAVING LIQUID TEMP
RETURN LIQUID TEMP
MIXED LIQUID TEMP
COOLING RANGE
AMBIENT AIR TEMP
LEAD SYSTEM
EVAPORATOR PUMP
EVAPORATOR HEATER
ACTIVE REMOTE CONTROL
SOFTWARE VERSION
SYSTEM 1 DATA
COMPRESSORS STATUS
RUN TIME
MOTOR CURRENT
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
SUCTION TEMPERATURE
OIL TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
COMPRESSOR LOAD STAGE
COOLER INLET REFRIG
LIQUID LINE SOLENOID
HOT GAS BYPASS SOLENOID
CONDENSER FAN STAGE
132
WATER
STANDARD
R-22
399 PSIG
375 PSIG
44 PSIG
130.0 °F
25.0 °F
36.0 °F
100 %FLA
600 SECS
REMOTE
AUTOMATIC
49.0 °F
58.2 °F
51.3 °F
42.0 +/-2.0 °F
74.8 °F
SYS 2
ON
OFF
NONE
C.RCP.09.00
OFF
0- 0- 0- 0 D-H-M-S
0 AMPS
0 %FLA
125 PSIG
131 PSIG
130 PSID
68.4 °F
68.8 °F
71.8 °F
3.4 °F
0
44.6 °F
OFF
OFF
OFF
SYSTEM 2 DATA
COMPRESSORS STATUS
RUN TIME
0- 0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS 87 %FLA
SUCTION PRESSURE
DISCHARGE PRESSURE
OIL PRESSURE
SUCTION TEMPERATURE
OIL TEMPERATURE
SAT SUCTION TEMP
SUCTION SUPERHEAT
COMPRESSOR LOAD STAGE
COOLER INLET REFRIG
LIQUID LINE SOLENOID
HOT GAS BYPASS SOLENOID
CONDENSER FAN STAGE
DAILY SCHEDU.L.E
S M T W T F S
FORM 150.52-NM2 (1001)
ON
57 PSIG
233 PSIG
218 PSIG
42.9 °F
102.8 °F
31.7 °F
11.2 °F
2
23.6 °F
ON
ON
3
*=HOLIDAY
YORK INTERNATIONAL