Electrical Notes; Control Power Supply; Electrical Legend - York MILLENNIUM YCAR0315 Installation Operation & Maintenance

Air-cooled reciprocating liquid chillers
Table of Contents

Advertisement

NOTES (refer to charts on pages 54 - 57)
1. Minimum circuit ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all
other loads included in the circuit, per N.E.C. Article 430-24. If a Factory-mounted Control Transformer is provided, add the following to
the system #1 MCA values in the YCAS tables: -17, add 15 amps; -28, add 12 amps; -40, add 7 amps; -46, add 6 amps; -58, add 5
amps.
2. The recommended disconnect switch is based on a minimum of 115% of the summation rated load amps of all the loads included in the
circuit, per N.E.C. 440-12A1.
3. Minimum recommended fuse size is based on 150% of the largest motor RLA plus 100% of the remaining RLAs. Minimum fuse rating
= (1.5 x largest compressor RLA) + other compressor RLAs + (# of fans x each fan motor FLA).
4. Maximum dual element fuse size is based on 225% maximum plus 100% of the rated load amps for all other loads included in the circuit,
per N.E.C. 440-22. Maximum fuse rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# of fans x each fan motor
FLA).
5. Minimum recommended circuit breaker is 150% maximum plus 100% of rated load amps included in the circuit. Minimum circuit breaker
rating = (1.5 x largest compressor RLA) + other compressor RLAs + (# of fans x each fan motor FLA).
6. Maximum circuit breaker is based on 225% maximum plus 100% of the rated load amps for all loads included in the circuit, per circuit,
per U.L. 1995 Fig. 36.2. Maximum circuit breaker rating = (2.25 x largest compressor RLA) + other compressor RLAs + (# fans x each
fan motor FLA).
7. The Incoming Wire Range is the minimum and maximum wire size that can be accommodated by unit wiring lugs. The (1), (2) or (3)
indicate the number of termination points or lugs which are available per phase. Actual wire size and number of wires per phase must
be determined based on ampacity and job requirements using N.E.C. wire sizing information. The above recommendations are based
on the National Electric Code and using copper conductors only. Field wiring must also comply with local codes.
8. A ground lug is provided for each compressor system to accommodate field grounding conductor per N.E.C. Article 250-54. A control
circuit grounding lug is also supplied. Incoming ground wire range is #6 - 350 MCM.
9. The field supplied disconnect is a "Disconnecting Means" as defined in N.E.C. 100.B, and is intended for isolating the unit from the
available power supply to perform maintenance and troubleshooting. This disconnect is not intended to be a Load Break Device.
10. Two-Compressor machines with single-point power connection, and equipped with Star (Wye)-Delta Compressor motor start must
also include factory-provided individual system circuit breakers in each motor control center. All 3 and 4 compressor machines equipped
with Star-Delta compressor motor start must also include factory-provided individual system circuit breakers in each motor control
center.
11. Consult factory for Electrical Data on units equipped with "High Static Fan" option. High Static Fans are 3.8 kW each.
12. FLA for "Low Noise Fan" motors: 200V = 8.0A; 230V = 7.8A; 380V = 4.4A; 460V = 3.6A, 575V = 2.9A.
13. Group Rated breaker must be HACR type for cU.L. machines.
VOLTAGE
Standard
Models without
Transformers
VOLT
MCA
DISC. SW
ACL
PW
N/A
RLA
FLA
ACL/LRA
YORK INTERNATIONAL

ELECTRICAL NOTES

CONTROL POWER SUPPLY

CONTROL
MINIMUM
UNIT
POWER
CIRCUIT
SUPPLY
AMPACITY
115-1-60
LEGEND (Pages 54 - 57)
= Voltage
= Minimum Circuit Ampacity
= Disconnect Switch
= Across-the-Line
= Part-Wind
= Not Available
= Running Load Amps
= Full Load Amps
= Across-the-Line Inrush Amps
MAXIMUM
NON-FUSED
DUAL-
ELEMENT
SWITCH
FUSE SIZE
20A
20A, 250V
30A, 240V
PW/LRA
= Part-Wind Inrush Amps
C. B.
= Circuit Breaker
HACR
= Heating, Air Conditioning and Refrigeration
MIN NF
= Minimum Non-Fused
S.P. WIRE
= Single-Point Wiring
Y-D
= Wye-Delta Start
X-LRA
= Across-The-Line Inrush Locked Rotor Amps
PW-LRA
= Part-Wind Inrush Locked Rotor Amps
FORM 150.52-NM2 (1001)
DISC.
SIZE
7
53