Glycol Correction Factors - York MILLENNIUM YCAR0315 Installation Operation & Maintenance

Air-cooled reciprocating liquid chillers
Table of Contents

Advertisement

GLYCOL CORRECTION FACTORS

The cooler is designed in accordance with ARI-550-
92, which allows for an increase in pressure drop of up
to 15% above the design value given above. Debris in
the water may also cause additional pressure drop.
When using glycol solutions, pressure drops are higher
than with water (see correction factors to be applied
when using glycol solutions). Special care must be taken
not to exceed the maximum allowed.
A =
Correction Factor
B =
Mean Temperature Through Cooler
C =
Concentration W/W
Excessive flow will cause damage to
the cooler. Do not exceed maximum
cooler GPM. Special care should be
taken when multiple chillers are fed
by a single pump.
YORK INTERNATIONAL
ETHYLENE GLYCOL
1.45
1.40
1.35
1.30
A
1.25
1.20
1.15
1.10
1.05
-10
-8
-6
-4
-2
PROPYLENE GLYCOL
1.8
1.7
1.6
1.5
A
1.4
1.3
1.2
1.1
1.0
-10
-8
-6
-4
-2
FORM 150.52-NM2 (1001)
50%
40%
C
30%
20%
10%
0
2
4
6
8
˚C
B
50%
40%
C
30%
20%
10%
0
2
4
6
8
˚C
B
LD03504
47
7