Technical Data
GENERAL UNIT DATA
Unit Cap. at 7.0°C water and 35°C ambient, kW
Number of Independent Refrigerant Circuits
Refrigerant Charge, R-22, Ckt.-1, kg.
Refrigerant Charge, R-22, Ckt.-2, kg.
Shipping Weight:
Aluminum Fin Coils, kg.
Copper Fin Coils, kg.
Operating Weight:
Aluminum Fin Coils, kg.
Copper Fin Coils, kg.
COMPRESSORS, SEMIHERMETIC RECIPROCATING
Quantity per Chiller
Nominal kW, Ckt.-1
Nominal kW, Ckt.-2
CONDENSERS, HIGH EFFICIENCY FIN / TUBE WITH INTEGRAL SUBCOOLER
Total Chiller Coil Face Area, m
Number of Rows
Fins per Meter
CONDENSER FANS
Number, Ckt.-1 / Ckt.-2
Fan Motor, HP / kW
Fan and Motor Speed, rev./sec.
Fan Diameter, mm
Fan Tip Speed, m/sec.
Total Chiller Airflow, l/sec.
EVAPORATOR, DIRECT EXPANSION
Water Volume, liters
Maximum
1
Water Side Pressure, Bar
Maximum Refrigerant Side Pressure, Bar
Minimum Chilled Water Flow Rate, Bar
Maximum Chilled Water Flow Rate, Bar
Water Connections, inches
1 Optional 21 Bar Waterside available
48

PHYSICAL DATA

SI UNITS
0315SC
329.6
2
55.6
55.6
4,445
4,874
4,656
5,084
2
194
194
2
17.84
3
512
3/3
2 / 1.8
19.3
900
55
40,492
193
10
24
7.9
37.9
8
MODEL NUMBER YCAR, 50 Hz
0345SC
0365SC
352.7
375.8
2
2
60.1
63.5
60.1
63.5
4,481
4,515
4,910
4,944
4,693
4,727
5,121
5,155
2
2
211
211
194
211
17.84
17.84
3
3
512
512
3/3
3/3
2 / 1.8
2 / 1.8
19.3
19.3
900
900
55
55
40,492
40,492
193
193
10
10
24
24
8.5
9.1
37.9
37.9
8
8
FORM 150.52-NM2 (1001)
0385SC
0415SC
400.9
426.9
2
2
69.2
79.4
69.2
79.4
4,766
4,952
5,195
5,380
4,981
5,115
5,410
5,548
2
2
246
246
211
246
17.84
17.84
3
3
512
512
3/3
3/3
2 / 1.8
2 / 1.8
19.3
19.3
900
900
55
55
40,492
40,492
193
193
10
10
24
24
9.9
11.4
37.9
37.9
8
8
YORK INTERNATIONAL

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents