protect against nuisance safety trips below 4°C (40°F)
and reduce the possibility of cooler damage due to freez-
ing during chiller operation, the unit Micro-Processor
will automatically unload the compressors at abnor-
mally low suction temperature (pressure) conditions,
prior to a safety shut down.
Process Brine Option – Process or other applica-
tions requiring chilled fluid below 4°C (40°F) risk wa-
ter freezing in the evaporator, which is typically over-
come by using anti-freeze. For these applications, the
chiller system incorporates brine (ethylene or propy-
lene glycol solution). The system design Leaving
Chilled Fluid Temperature must be provided on the
order form to ensure proper factory configuration.
BASIC PART NUMBER
BASE MODEL NUMBER:
YCAR0415SC46PAA
1 2 3 4
5 6 7 8
BASE PRODUCT TYPE
NOMINAL CAPACITY
Y
: YORK
0 #
C
: Chiller
1 #
A
: Air-Cooled
R
: Reciprocating
60 Hz: Nominal Tons = Even Number
50 Hz: Nominal kW = Odd Number
Nominal Capacity = Marketing Capacity + 5% (rounded)
YORK INTERNATIONAL
UNIT NOMENCLATURE
NAMEPLATE ENGINEERING DATA
9
UNIT DESIGNATOR
#
#
S
: Standard Unit
#
#
Thermal Storage Option – Thermal Storage re-
quires special capabilities from a chiller, including
the ability to 'charge' an ice storage tank, then pos-
sibly automatically reset for operation at elevated
Leaving Chilled Fluid Temperatures as required by
automatic building controls. The Thermal Storage
Option provides Ice Storage duty Leaving Chilled
Fluid setpoints from -4°C to -10°C minimum (25°F
to 15°F minimum) during charge cycle, with Reset
range to normal supply fluid temperature.
• Power Factor Correction Capacitors – Provides
compressor motor full load correction to a minimum
of 0.90 power factor.
10
11 12 13
REFRIGERANT
VOLTAGE/STARTER
: 380-415/3/50
B
: R-407C
5
0
C
: R-22
: Across-The-Line
X
: Part-Wind
P
FORM 150.52-NM2 (1001)
14 15
DESIGN/DEVELOPMENT LEVEL
A
: Design Series A
A
: Engineering Change
or PIN Level
- continued on page 30
25
2