Figure 4-16 Fault-Tolerant Digital Input Module In 1-Out-Of-2 Configuration With One Encoder - Siemens SIMATIC PCS 7 CPU 410-5H System Manual

Process control system / process automation
Table of Contents

Advertisement

I/O configuration variants
4.7 Connecting redundant I/O to the PROFIBUS DP interface
Using redundant digital input modules with non-redundant encoders
With non-redundant encoders, you use digital input modules in a 1-out-of-2 configuration:
Figure 4-16
The use of redundant digital input modules increases their availability.
Discrepancy analysis detects "Continuous 1" and "Continuous 0" errors of the digital input
modules. A "Continuous 1" error means the value 1 is applied permanently at the input, a
"Continuous 0" error means that the input is not energized. This can be caused, for example,
by a short-circuit to L+ or M.
The current flow over the chassis ground connection between the modules and the encoder
should be the minimum possible.
When connecting an encoder to several digital input modules, the redundant modules must
operate at the same reference potential.
If you want to replace a module during operation and are not using redundant encoders, you
will need to use decoupling diodes.
If you do not use terminal modules, see the interconnection examples in the Appendix
Connection examples for redundant I/Os (Page 337).
Note
Remember that the proximity switches (Beros) must provide the current for the channels of
both digital input modules. The technical data of the respective modules, however, specify
only the required current per input.
82
Fault-tolerant digital input module in 1-out-of-2 configuration with one encoder
CPU 410-5H Process Automation
System Manual, 09/2014, A5E31622160-AB

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents