Code list
70
Calibration
Additional alarm at the fault
alarm contact!
71
General parameters
Start-up parameters
72
73
Internal device error 1
HART parameters
74
75
Info parameters
No emergency mode
76
88
EB 8384-3 EN
Error in the production calibration data. Subsequently, the device
runs on default values
Remedy Return the positioner to SAMSON AG for repair.
Parameter errors that are not critical for the control.
Remedy Confirm error.
Check and, if necessary, reset required parameters.
Start-up parameter errors
Remedy Confirm error, perform reset and re-initialize the positioner.
Internal device error
Remedy Return the positioner to SAMSON AG for repair.
Error in the HART
function.
Remedy Confirm error.
Check and, if necessary, reset required parameters.
Error in the info parameters that are not critical for the control
function.
Remedy Confirm error.
Check and, if necessary, reset required parameters.
The travel measuring system of the positioner has a self-moni-
toring function (see Code 62).
A controlled emergency mode is not available on certain actua-
tors, such as double-acting actuators. For this reason, the
positioner moves to the fail-safe position when a measuring error
occurs. During the initialization, the positioner checks whether
the actuator has such a function or not.
Remedy Merely information, confirm, if necessary.
No further action necessary.
®
parameters that are not critical for the control