Samson 3730 Series Mounting And Operating Instructions page 81

Electropneumatic positioner with hart communication
Table of Contents

Advertisement

33*
Fault alarm with "Mainte-
nance alarm" or "Mainte-
nance required" condensed
status
NO [YES]
ESC
34*
Closing direction
CL [CCL]
ESC
Blocking position
35*
[0] mm/° /%
ESC
36*
Reset
[OFF]
RUN
ESC
Position transmitter
37
Yes No
38*
Inductive alarm
[NO]
YES
ESC
39
System deviation e info
–99.9 to 999.9 % ,
Transit time Open info
40
0 to 240 s [0]
41
Transit time Closed info
0 to 240 s [0]
42
Auto-w info
0.0 to 100.0 % of the span
4 to 20 mA
Firmware info
43
Xxxx
NO: Fault alarm only with "Maintenance alarm" condensed
status
YES: Fault alarm only with "Maintenance alarm" condensed
status and with "Maintenance required" condensed status
CL: Clockwise, CCL: Counterclockwise
Turning direction in which the valve is moved to the CLOSED po-
sition (view onto the rotary switch motion when the positioner
cover is open).
Needs only be entered in initialization mode SUb (Code 6).
Entering the blocking position.
Distance up to the CLOSED position.
Only necessary in initialization mode SUb.
Resets all start-up parameters to default (factory setting).
Note: After setting RUN, the positioner must be re-initialized.
Display only,
indicates whether the position transmitter option is installed.
Indicates whether the inductive limit switch option is installed or
not.
Display only,
indicates the deviation from the set point position (e = w–x).
Display only,
minimum opening time is determined during initialization
Display only,
minimum closing time is determined during initialization
Display only,
indicates the supplied automatic reference variable corre-
sponding 4 to 20 mA.
Display only,
indicates the device type and the current firmware version of the
positioner in alternating sequence.
Code list
81
EB 8384-3 EN